6
No.
Name
Description
EK21
Positions proved
0 - Drives have stopped moving, ready for
position prove test.
1 - Ready for position prove test but drives still
moving.
EK22
Fault alarm
0 – No un-muted alarms (faults) present.
+1 - Un-muted fault alarm present (prefix : F)
+2 - Un-muted limit alarm present (prefix : L)
+4 – Un-muted flue-monitoring alarm present
(faults 50 to 59).
EK23
Oxygen Trim Enable
0 – Oxygen trim off or not working.
1 – Oxygen trim on and working.
EK25
CAN_TX Failures
A count of the number of times the can bus
controller has failed to send a message since
power-up. This should be zero unless there has
been a problem.
EK26
Commission status
Current commissioning mode, where :
0 - Normal run mode.
1 - Adjust ratio mode.
2 - Commission ratio mode.
EK27
Commission setpoint
The current setpoint being commissioned.
0 - Closed setpoint.
1 - Purge setpoint.
2 - Ignition setpoint.
3 - Low fire setpoint.
4 - 24 - profile setpoints
EK28
Commission Setpoints entered
The number of setpoints that have been
successfully entered during this commission ratio
session.
EK29
Modulation rate (%)
The current modulation rate of the burner.
0 = Low Fire
100 = High fire
EK30 Burner
Status
Status of the start-up sequence. See section 4.2
of Fireye Bulletin PPC-6001
EK31
Fuel Profile Selected
The currently selected fuel profile.