61
®
MODBUS MESSAGE TABLE
Table 6:
HOLDING
REGISTER
MESSAGE
ADDRESS
WORD
REQUESTED
WORD
RESPONSE
VALUE
40001
00
1
STATUS
83 (053H) = RUN;
202 (0CAH) = LOCKOUT
40002
01
1
MSGN
Current message being displayed
(see Table 9)
40003
02
1
GSTAT
Defines Timer Type
40004
03
1
TIMER
Time in seconds
40005
04
1
FLAME
Flame Signal
40006
05
1
LOGSTAT
Current logic module, PURGE, PTFI, AUTO
(see Table 8)
40007
06
1
INPUTS
Input limits state
40008
07
1
OUTPUTS
Output relays state
40009
08
2
SYSMINS
System on minutes
40011
10
2
BNRMINS
Burner on minutes
40013
12
2
CYCLES
Completed Burner Cycles
40015
14
1
LOCKOUT COUNT
Stored Lockout Count
40016
15
6
LOCKOUT HISTORY
Beginning of Last 10 Lockouts
Most Recent Lockout Data
Returns complete lockout description of
stored lockout history.
Includes lockout message (1), lockout module (1),
@ burner hours (2), and @ burner cycles (2)s
40022
21
6
2nd Most Recent Lockout Data
40028
27
6
3rd Most Recent Lockout Data
40034
33
6
4th Most Recent Lockout Data
40040
39
6
5th Most Recent Lockout Data
40046
45
6
6th Most Recent Lockout Data
40052
51
6
7th Most Recent Lockout Data
40058
57
6
8th Most Recent Lockout Data
40064
63
6
9th Most Recent Lockout Data
40070
69
6
10th Most Recent Lockout Data
40076
40079
75
78
4
40080
40090
79
89
11
N/A
Reserved for Fireye use
INTERLOCK ANNUNCIATOR
40901
900
1 - 3
YZ300 Interlock
Annunciator registers
(see Table 7)
Returns lower, middle and upper interlock
annunciator (YZ300) registers.
40902
901
1 - 2
Returns middle and upper interlock annunciator
(YZ300) registers.
40903
902
1
Returns upper interlock annunciator
(YZ300) register.
Summary of Contents for BurnerLogiX BLL510
Page 79: ...79 NOTES...