66
®
EXPLANATION OF LOGSTAT
LOGSTAT is an indication of what logic module the control is currently operating in during its cycle
and is used for diagnostic purposes only. If a lockout occurs the current value of LOGSTAT is stored
as part of the lockout information. The message displayed corresponds to the current logic module.
Table 8:
Logstat represents the current software module the BurnerLogix is currently executing.
LOGIC DISPATCHER
VALUE MODULE
FUNCTION
DEC
HEX
1
01H
STANDBY
Idle state
2
02H
BLOWER ON
1/2 second period after operating control closes when blower motor is energized
3
03H
PURGE
Open Damper Purge or waiting for air flow and/or high fire switch to close
4
04H
PURGE
Low Fire Purge
5
05H
PTFI
Pilot Trial for Ignition
6
06H
PTFI
Pilot Trial for Ignition for YP3XX programmers
7
07H
PTFI
If PTFI is greater than 5 seconds and early spark termination is not needed
8
08H
PTFI
If PTFI is greater than 5 seconds and early spark termination is needed
9
09H
PILOT
Pilot Hold, YP138 only
10
0AH
MTFI
Main Trial for Ignition
11
0BH
MTFI
Main Trial for Ignition with terminal 5 de-energized
12
0CH
AUTO
Delayed valve on
13
0DH
AUTO
AUTO
14
0EH
AUTO
On YP138 programmer, hold for 20 seconds with terminals 6 and 7 energized
15
0FH
AUTO
On YP138 programmer, when terminal 21 first energized, wait for M-D to close
16
10H
POSTPURGE
Post Purge
17
11H
POSTPURGE
Post Purge period if flame fail lockout
18
12H
POSTPURGE
Idle state if unit is in lockout
19
13H
PRE PURGE
AUX
LIMIT #3
AUX
LIMIT #2
AUX
LIMIT #1
OPERATING
CONTROL
HIGH
WATER
LOW
WATER
42
41
40
L2/N
HIGH OIL
TEMP.
LOW OIL
TEMP
LOW OIL
PRESS
46
47
AIR
FLOW
AUX
LIMIT #7
60
AUX
LIMIT #6
AUX
LIMIT #5
AUX
LIMIT #4
HIGH
PRESSURE
59
58
57
56
43
44
AUX
GAS
HIGH GAS
PRESSURE
52
50
LOW GAS
PRESSURE
51
LOW ATOM
MEDIA
48
53
45
OIL SELECT
GAS SELECT
49
SIMULTANEOUS FIRING
54
HIGH
TEMP
55
L1
3
E
P
See Bulletin YZEM-3001
Default wiring for YZ300 Interlock Annunciator