26
®
9.
Press the RESET/MDFY key to enter modify mode.
10.
Press the UP arrow to move the value to 5.
11.
Press the RESET/MDFY key to save the value.
12.
Press the NEXT key and the display must read SET LVL1 PW to indicate the password was
entered correctly. If not start over at step 4.
13.
Pressing the MODE key will exit the BOILER PARMS sub-menu and return to the main menu.
The password will remain enabled for 5 minutes or an additional 5 minutes every time any key on the
keypad is pressed.
FIGURE 7.
BOILER PARMS SUB-MENU
UNITS OF MEASURE / DISPLAY UNITS
The BurnerLogix system provides the user with the option of working in ENGLISH or METRIC
units. This parameter applies to both pressure and temperature units. With all boiler parameters set to
UNUSED (out of the box condition), the item UNITS OF MEASURE will be available to select
ENGLISH or METRIC. After this choice has been made and the pressure or temperature sensor has
START HERE FROM BOILER PARMS >
Scrolls through menu, clockwise, increment value
Keypad Legend
CTRL VAR CONFIG
MODE
MODIFY TO CHANGE
PCV INPUT UNUSED
AUX 1 CONFIG
MODE
MODIFY TO CHANGE
AUX 2 CONFIG
MODE
MODIFY TO CHANGE
AUX 2 USE UNUSED
NEXT
Scrolls through menu, anti-clockwise, decrement value
BACK
MODE
MODIFY
RESET
Exits Sub-Menu
Allows parameter to be modified/saved
AUX 1 USE UNUSED
UNITS OF
MEASURE
DISPLAY UNITS
ENT LVL2 PW
LAG 1 CONFIG
MODE
MODIFY TO CHANGE
LAG 1 MODE UNUSED
MOD USE
AUTO
MOD MAX 100
SYS TEST 0
ENT LVL1 PW
LAG 2 CONFIG
MODE
MODIFY TO CHANGE
THML SHK CONFIG>
MODE
MODIFY TO CHANGE
LAG 2 MODE UNUSED
THML SHK UNUSED
PRESS
PRESS
PRESS
PRESS
OR
Note 1
MOD POS visible only if MOD USE is set to MAN.
Note 2:
MOD MAX located in this menu pertains to LEAD
operating mode. See LAG1 and LAG2 for alternate
MOD MAX settings.
See Note 2
MOD POS 100
See Note 1