25
®
program four basic steps to get the boiler up and operational, while becoming familiar with the oper-
ation and programming of the control. These four steps are:
1.
Enter the 2 level password.
2.
Select and program the appropriate sensor ranges.
Note: A general rule to follow when selecting the appropriate range for the sensor is the expected
value of the monitored pressure or temperature should fall between 40-70% of upper range of the
sensor. For example, a steam boiler maintains 20 pounds pressure, select the BLPS-30 Pressure
Sensor with a 0-30 PSIG range.
3.
Program the desired operating control function (setpoint, cut in, and cut out).
4.
Program the modulating control function (mod range, mod max, mod use.
If necessary or desired, program cold start protection (thermal shock).
FIGURE 6.
SET THE PASSWORD
The BOILER PARMS sub-menu contains the parameters that controls the operation of the burner
while the burner is in either standby or main firing. To prevent unauthorized entry and modification
of system setpoints and operating parameters, these parameters are password protected
IMPORTANT: THE BURNERLOGIX Z SYSTEM IS SHIPPED WITH THE SOFTWARE
PASSWORD SET BY THE FACTORY. THE USER CANNOT PROGRAM ANY SET-
POINTS UNTIL THE PASSWORD IS ENTERED. FACTORY DEFAULT PASSWORDS
ARE:
LEVEL 1 PASSWORD = 2
LEVEL 2 PASSWORD = 5
To enter the password of 02 for Level 1 and 05 for Level 2:
1.
From the BurnerLogix main menu (see Figure 4), use the NEXT or BACK keys to get to
BOILER PARMS>.
2.
Press the MODE key to access the BOILER PARMS sub-menu.
3.
The first item displayed will be either UNITS OF MEASUREMENT or DISPLAY UNITS.
4.
Press the NEXT key to display ENT LVL1 PW.
5.
Press the RESET/MDFY key to enter modify mode.
6.
Press the UP arrow to move the value to 2.
7.
Press RESET/MDFY to save the value.
8.
The display will automatically advance indicate ENT LVL2 PW.
LOW
FIRE
D
E
STEAM PRESSURE (PSIG)
11
12
13
14
15
16
17
MOD
MAX
C
HIGH
FIRE
100%
20mA
MOD
MAX
(e.g.: 80%)
0%
4mA
MOD RNGE = 3 PSIG
STM SP = 15
CUT OUT = 2
CUT IN = 0
BOILER
FIRING
RATE MOTOR
OPERATING CONTROL
OPENS AT 17 PSIG AND
CLOSES AT 15 PSIG
FIRING RATE
POSITION