PROGRAM SET UP SUB-MENU
The sub-menu "PROGRAM SETUP" allows the user to review the various operational settings of
the programmer module (e.g. programmer type, purge timing, etc.) and some instances modify the
operational parameters to suit the application requirement. The MODE key is used to enter and exit
the sub-menu and the NEXT and BACK keys are used to scroll through the menu as well as change
the operational parameter.
FIGURE 5.
TO VIEW AND MODIFY A PROGRAMMABLE PARAMETER:
Use the NEXT or BACK key to scroll to PROGRAM SETUP see Figure 4. Press the MODE key to
enter the sub-menu showing all program setup parameters. Pressing the MODE key while in the sub-
menu will exit the sub-menu, and the next main menu item will be displayed. While in the sub-menu,
pressing the NEXT key will scroll forward through the sub-menu. Pressing the BACK key will scroll
backward through the sub-menu. When a modifiable parameter is displayed, the top line will indicate
MDFY TO CHANGE while the bottom line will indicate the current item and its current value.
Pressing the RESET/MDFY key will allow the displayed parameter to be modified. The item to be
modified will move to the top line while its value will remain on the bottom line. At an infrequent
rate, the top line will indicate MDFY TO SAVE. Use the NEXT or BACK keys to select the value to
suit the application and when done, press the RESET/MDFY to save the value to memory.
P
MDFY TO CHANGE
FLM FAIL TIME 4 SEC
AMP IR
PROGRAMMER YP100
DO IR LEARN NO
LOCK SETTINGS NO
START HERE
MODE
PROVE 3-P OPEN N
MDFY TO CHANGE
COUNT METHOD DOWN
MDFY TO CHANGE
PURGE 0:30
UNIT ADDRESS 1
BAUD RATE 9600
PROVE M-D TFI NO
M-D WAIT 10m YES
POST PURGE 0:15
PROVE M-D OPEN NO
PROVE M-8 OPEN NO
TERMINAL 6 INTRP
PTFI * MTFI TIMING
FROM
MAIN
MENU LOOP
PRESS
KEY FROM MAIN MENU LOOP
MODE
PRESS
KEY AT ANYTIME TO EXIT SUB-MENU
Note:
ZB110IR prior to
version 12 only