STOVE SITING WITH CLOSURE PLATE:-
Method 1
A non combustible hearth must be provided beneath the appliance and must extend outwards all around
the appliance base.
The stove should be positioned onto a solid non combustible hearth with a minimum thickness of 12mm and
must have a clearly defined edge (change of level) to discourage placing of any combustible materials on or
partially over it.
The stove can be levelled if necessary by using the screws in the legs with a 14mm spanner at each corner.
The Closure plate must be securely fastened to the fire place opening and sealed using a suitable heat
resistant material so no products of combustion can leak out back into the room. The front of the fireplace
should be flat over an area sufficient to ensure a good seal with the closure plate. The flat surface should
extend for a height equal to that of the closure plate plus 20mm and for a width equal to that of the closure
plate plus 40mm.
The closure plate measures 600mm high by 460mm wide & must be fitted and sealed to the fireplace
opening using a suitable heat resistant material.
CHECKING GAS SOUNDNESS
Turn on the gas supply to the appliance and check for soundness in accordance with current codes of practice.
Turn off the gas supply at the external Isolation valve.
Remove the pressure test point screw from the inlet elbow and connect the pressure gauge.
Turn on the gas to the appliance at the Isolation valve.
Rotating the control to the ignition position and push in to allow the air in the pipe to be purged.
Rotating the control knob a few times, check that the electrode is sparking at the gap between the
thermocouple tip and the electrode; continue until pilot ignition is established.
Depress the control knob slightly and rotate anticlockwise until the raised pointer is aligned with the large
flame symbol on the control panel.
Check the inlet pressure is 20mbar Natural gas (G20) or 37mbar Propane (G31).
Turn off gas supply, at the isolation valve. Disconnect the pressure gauge and replace the pressure test point
screw.
Turn on the supply to the appliance and check the pressure test point for soundness with detection fluid.
SECTION TEN Checking Operation of Fire (Installation Instructions)
LAY FUEL BED
Important: -
Refer to the ‘Heath & Safety Notice located on page 5 of this booklet before laying or replacing any refractory
material.
In the event of replacing fuel bed components please use only the specified number of components as illustrated. Only
use fuel bed component provided for this appliance. In the interest of safety and efficiency
of your appliance when
replacing the fuel bed it is essential that the existing fuel bed be removed and the new components are
replaced correctly as a complete set.