LT6498 (ISS 2)
Distances from NON-combustible materials:
The stove can be recessed in a suitable sized non-combustible fireplace but a permanent free air gap of at
least 50mm must be left around the sides and top and at least 45mm at the back of the stove to obtain
reasonable heat output and for access to the stove for removal and maintenance. A clearance of 150mm will
give a better heat output
When installing the FIRELINE FXW/FPW Gas Stove, careful consideration should be made to the siting of the
appliance as a spillage test will need to be carried out at the Draught Diverter at the rear of the stove.
When siting into an Inglenook, consideration should be made for access to the rear of the appliance, either
from to top or sides of the stove so a spillage test can be witnessed. A small mirror may be required.
A minimum of 45mm needs to left between the rear of the stove and the closure plate or back wall for correct
operation of the stove, this will be attained when the two Stand off Brackets are attached at the bottom rear
of Stove.
Important: - The Standoff brackets must be attached to the bottom rear
of the Stove prior to installing, Please see above picture.