The FC410LPBS devices are synchronised, but not
synchronous with other FireClass sounders and
beacons of the FC400 series.
The first flash of the beacon is synchronised with the
start of the tone. The FC410LPBS devices have a built
in two port isolator.
FC430LPSB and FC430LPASB
loop powered addressable
sounder beacon base
The FC430LP series of loop powered addressable
sounder and sounder- beacons are designed to
be driven from an FC503 or FC506 control panel
through the addressable loop. Tone, volume,
and flash rates are set in the FireClass FC500
(FC501_FC503_FC506) Console. The sounder has
four volume settings High (90 dB ±3), Mid High (80
± 3dB), Mid Low (70 ± 3 dB) or Low (60 dB ± 3). The
beacon has two flash rates Slow Flash (1/2 Hz) or
Fast Flash (1 Hz). The FC430LP Series have a built-in
line isolator.
FC430LPBSB Loop powered
addressable sounder/beacon
base (EN54-23)
The FC430LPBS series of loop powered addressable
sounder and sounder- beacons are designed to be
driven from an FC503 or FC506 control panel from
the addressable loop. Tone, volume, and flash rates
are set in the FireClass FC500 (FC501_FC503_FC506)
Console.
The sounder has four volume settings High (90dB
±3), Mid High (80 ±3dB), Mid Low (70 ±3dB), or Low
(60 dB ±3). The beacon has two flash rates Slow
Flash (1/2 Hz) or Fast Flash (1 Hz). The FC430LPBS
Series have a built-in line isolator.
Table 60: EN54-2
FireClass product
code (Current Dev.)
FireClass device
name (Current Dev.) Description
FireClass
product code
(EN54-23 Dev.)
FireClass
device name
(EN54-23 Dev.)
516.800.758
FC430LPASB
Loop powered beacon
sounder base
516.800.973
FC430LPBSB
516.800.763
FC410LPAVR
Loop powered beacon
sounder (indoor use) red
516.800.970
FC410LPBS-R
516.800.764
FC410LPAVW
Loop powered beacon
sounder (indoor use)
white
516.800.971
FC410LPBS-W
516.800.766
FC410LPAV
Loop powered beacon
sounder IP65 (outdoor
use)
516.800.972
FC410LPBS
Note:
It is possible to substitute old devices with the
correspondent new ones (EN54-23) and to keep
the same program data. When the old device is
physically removed from the loop, the control
panel will signal the No answer fault. When the
new device with the same address is connected
to the loop, the control panel will restore the
No answer fault and automatically update its
internal database with the new device type.
It is not possible to substitute new EN54-23
devices with old devices that are not EN54-23
approved.
FC410SNM Sounder notification
module
The FC410SNM Sounder notification module
provides an output, in response to a command
signaled from a controller, to activate a number of
polarized and suppressed sounders. The sounders
are powered from an independent power supply
and the module is capable of passing up to a
maximum current of 2 A. For example, 24 VDC 50
mA company sounders or a mixture of different
FC503 and FC506 Addressable Fire Control Panels
78