Note:
The panel on board Open Collector
outputs (OC1, OC2) may not be programmed to
act as SC1.
Panel Alarm Trigger
When the
PANEL ALARM TRIGGER?
option is set
to YES, the relevant output becomes active on the
panel alarm condition. Alternatively, a more specific
trigger condition may be defined for the output. The
default setting is YES.
Disablement Trigger
The
DISABLEMENT TRIGGER?
option activates the
relevant output if any system part is disabled. The
default setting is NO.
Note:
This parameter is made available only
if the parameter PANEL ALARM TRIGGER for
the same output is set to NO. Setting the
parameter to YES will end the programming
sequence for that output. Outputs which have
this option programmed are not silenceable.
This feature is also available for Panel FIRE relay
and FC410RIM, FC410SIO, FC410MIO, FC410QMO,
FC410QRM, FC410QIO loop modules.
•
OUTPUT NAME
•
TRIGGER ZONE 1
•
TRIGGER ZONE 2
•
TRIGGER EVENT
•
SILENCEABLE
•
MONOSTABLE
Figure 30: Programming SC active on
disablements
Callout
Description
1
Control panel name
2
Output number
3
Access level
4
Control panel status
5
If blinking, the control panel is
working properly
6
Output type
7
Output number
8
Insert output label
FC503 and FC506 Addressable Fire Control Panels
55