status remains until the Night Mode Silence time
expires.
At default, the system is set to Day Mode. During
Day Mode, silenced alarms are not unmuted
automatically.
Fault
This control panel can detect and signal the faults
shown in Table 2. Fault conditions signals are:
•
Control panel buzzer; 1 second of sound at
660 Hz and a 1 second pause.
•
The Fault LED and relative Fault LED is on.
•
A Fault message on the LCD display.
•
Activation of the Fault output.
•
Activation of other outputs including SC2, OC1
or OC2 if programmed.
The Fault output and any additional programmed
fault outputs automatically return to standby status
when the fault conditions clear.
Under certain circumstances, fault conditions may
clear spontaneously. If this occurs, the memory
stores the event until you reset the control panel.
Blinking on the Fault LED indicates stored fault
events.
Silence
This control panel provides a
Silence
key that can
restore the Silenceable outputs to Standby status.
When the Silence LED is on, this indicates the Silence
status.
The Silence status remains until one of the following
occurs:
•
You press the Silence key again
•
The programmed Night Mode Silence time
expires when the control panel operates in
Night Mode.
•
A new alarm condition is detected.
Table 2: Description of faults
Message
Problem
Mains fault
The control panel is not
powered from the mains
Battery
The control panel’s batteries
charger is not working
correctly
Low battery
The control panel batteries are
empty
Earth
Leakage to earth
Table 2: Description of faults
Message
Problem
24A Output
Shorted 24A Output
24R Output
Shorted 24R Output
Firmware main
contr.
Checksum fault
Not programmed
dev
Loop device without address
Loop return open Loop negative signal open
Loop signal open Loop positive signal open
Loop local short
Local short on loop controller
Loop right short
Right side loop short
Loop left short
Left side loop short
Non answer
Loop device does not answer
Dirty level
Smoke detector only; the dirty
threshold has been exceeded
Short circuit
Short circuit on input module
Open circuit
Open circuit on input module
Power supply
Main fault
Wrong value
A loop device has an incorrect
value
Stuck output
An output module relay is not
switched
Same address
Several loop devices have the
same address
Wrong Type
Different loop device from that
programmed in the panel
IP Communicator Communication lost with IP
controller
IP receiver
Communication lost with IP
receiver
PSTN
communicator
The communication with PSTN
controller is lost
Telephone line
Telephone line fault
LOG Full
LOG fault
PSTN Action not
Ack.
A PSTN action not
acknowledged
SC X short
SC x= (1 or 2) short circuit
SC X open
SC x (1 or 2) open terminal
Prog.data main
cont
Data programming checksum
fault
Prog.data
tel.board
Aux Controller data
programming checksum fault
FC503 and FC506 Addressable Fire Control Panels