the FireClass FC500 (FC501_FC503_FC506) Console.
The FC421CP callpoint meets the requirements of
EN54 Pt.11. The FC421CP is fitted into a standard
weatherproof break glass callpoint housing.
FC430SAB/SAM Sounder base
address modules
The FC430SAM and FC430SAB sounder base address
modules are designed to control a loop powered
sounder base for use with the FC system. The
FC430SAB variant has an integral beacon. They may
also be used to drive a relay base. The units are
used to supply the address decoding in place of a
detector, thus providing a loop powered sounder
when used in conjunction with an FC430SB. The
modules are colour matched to the sounder bases.
The FC430SAM and FC430SAB are locked into
the base using the locking device integral to the
sounder base.
FC430SB Loop low power
sounder base
The FC430SB loop low power sounder base
provides an additional sounder function on the
FC addressable loop circuit. The FC430SB loop
low sounder base requires an associated detector
in order to operate, as it uses the address of the
detector that is fitted to it. Removal of the detector
or loss of power to the loop will cause the sounder
to cease operating. A maximum of 30 sounder bases
at full volume may be connected to the loop.
4B-I Isolator base
The FC460 and FC400 series detectors, as supplied,
use a common 4B-I isolator base assembly. The
base may be fixed directly to:
•
British (fixing centers 50 mm) or European
(fixing centers 70 mm) conduit box
•
FC450EMB European mounting box
•
Directly to the ceiling
FC490ST Loop service tool
The FC490ST loop service tool is used to program
the loop address into FC addressable devices.
The FC490ST displays information and performs
tests on devices. It has a 32 character backlit LCD
alphanumeric display, arranged in 2 rows of 16
characters and four soft keys, F1, F2, F3, and F4.
Power for the FC490ST is derived from 4 AA size
nickel metal hydride rechargeable batteries. You
can also run it from an unreg12 VDC input.
Examples include a car cigarette lighter connection
or a 110 230 VAC mains adaptor which will also
recharge the batteries.
FC410CIM Contact input
module
The FC410CIM FC addressable contact input
module is designed to monitor fire contacts such
as extinguishing system control, ventilation control,
or fire door control etc. The FC410CIM can be
configured as:
•
Two spur circuits (Class B) monitoring
multiple normally open contacts, with short
circuit giving a fault output
•
Two spur circuits (Class B) monitoring single
normally closed contacts, with short circuit
giving a fault output
•
Two spur circuits (Class B) monitoring
multiple normally open contacts, with short
circuit giving an alarm
FC410DIM Detector input
module
The addressable FC410DIM provides the ability to
connect and interface one or two zones of 24 VDC
2-wire conventional detectors (non-addressable) to
the fire alarm controller.
The FC410DIM monitors the status of detectors and
wiring to detectors and signals detector and wiring
status back to the controller.
FC410RIM Relay interface
module
The FC410RIM relay interface module provides one
volt-free relay changeover contact on a latching
relay. The relay is controlled by a command sent
from the FC fire controller through the addressable
loop. The relay state (activated, deactivated, or
stuck) is returned to the controller.
FC410BDM Beam detector
module
The FC410BDM Beam Detector Interface Module is
designed to interface FIRERAY 50 Beam Detectors to
the FC Digital Addressable Loop. It cannot be used
with other types of beam detectors. The FC410BDM
monitors the Fire and Fault contacts and monitors
for open and short circuits on the connections
between the interface and the beam detector. For
FC503 and FC506 Addressable Fire Control Panels