2. Use the left and right arrow keys or the ^
symbol under the name of the selected
module to select the FC500MFI modules to be
configured.
3. Enable a FC500MFI module with the
Up
arrow or disable it with the
Down
arrow. The
module name will appear in uppercase if
enabled.
4. Press the
ENTER
key to confirm.
Result
In the ANALYZE status (lev.1 level), an acronym is
used to display the related status. The acronyms
are:
•
OK!
The net. device is sensed as connected
and working
•
ko!
The net. device is sensed as not connected
•
FAU
The net. device is faulty
•
DIS
The net. device is disabled
•
-- The net. device is not configured in the
network
•
OLD
The net. device has an obsolete FW
version.
For an explanation of the features and
programming addresses, refer to the
FC500MI
module
document.
In this phase the keypad and keys have the
following functions:
Alphanumeric keypad
No function is related to the alphanumeric keypad.
Cursor keys
Table 46: Cursor key functions in network
Key
Function
Up
Use to enable the selected
module
Down
Use to disable the selected
module
Right
Use to select the module
Left
Use to select the module
ESC and ENTER keys
Table 47: ESC and ENTER key function in network
Key
Function
ESC
Use to abort the programming
procedure
ENTER
Use to confirm the
programming procedure and
leave the screen
Figure 32: Display to enable the FC500MFI
module
Callout
Description
1
Symbol shows the selected module
to enable
6 Key – Map Device
The Map Device option activates the On Demand
Map Device feature to modify the devices
addressing scheme in a working system. See Figure
26, 0.
Use the On Demand Map Device option in a system
where the addressing scheme is well known,
because all devices are singularly addressed using
the service tool or the device mapping feature
embedded in the loop enroll process (
1
key).
This feature is not intended to acquire new devices
on the loops. Use the Enroll feature to acquire new
devices on the loops.
In contrast to the device mapping feature
embedded in the loop enroll process, the On
Demand version does not automatically modify
devices labels and assigned zone.
Note:
All the devices, including the unique type
devices are added to the activated list. The only
output type devices are treated as described in
the standard device mapping procedure. They
will be singularly activated when selected in the
list.
In this phase the keypad and keys have the
following functions:
FC503 and FC506 Addressable Fire Control Panels
57
Johnson Controls - CONFIDENTIAL