Table 36: Values table of the programming devices
Heat detector
Smoke detector
Smoke + Heat
detector
Heat + CO detector Heat + Smoke + CO
detector
Generic digital
input channel (loop
devices)
Generic digital
output channel
(loop devices)
DDM input channel
Working mode
B NO
C NO
C NC
Input label
Output label
Input label
Assigned zone
Trigger zone#1
Assigned zone
Trigger Zone#2
Trigger zone event
ALA Alarm
DLY Delay to alarm
WAR warning
FAU Fault
TST Test
DK Double Knock
Silencable
On
Off
Trigger zone#3
Trigger zone#4
Trigger point#1
Trigger point#2
Trigger point#3
Note:
The underlined options are the default
options
Loop devices programming screen
After selecting the loop and the device, the option
LED displays. See Figure 27. The LED option allows
for the location of the selected device in the site,
lighting its LED when the option ON is selected.
Note:
Press the
ENTER
key to validate the
selection. If the device has no LED, the device
sounder or beacon is activated. The option
OFF removes the device signalling. The option
SKP exits the feature and moves to the normal
device programming sequence.
Remote LED
After programming other parameters, it is possible
to enable the activation of the programmable
Remote LED of a detector.
The detector has an output used to drive the
Remote LED. The output is activated only for the
detector alarm to which it belongs. It is possible
to program it to activate for other events as the
activation occurs for other panel outputs and for the
detector alarm to which it belongs.
Note:
The Remote LED can also be
programmed on the FireClass FC500
(FC501_FC503_FC506) Console in the
programming screen for the detectors.
Separated programming of the sounder
and beacon
Select Separated programming of the sounder
and beacon when any of the following devices are
selected:
FC410LPAV
(all versions)
FC430LPASB
FC430SAB
(with
FC430SB
)
FC503 and FC506 Addressable Fire Control Panels
51