NFPA Standard-Specific Requirements
78
Document #51003 Rev.E 01/11/02 P/N 51003:E
NFPA Signaling Systems for Central Station Service (Protected Premises Unit)
The following figure illustrates an example of Central Station/Remote Station Reporting using an MS-5012. The
relay contacts from the MS-9200 may be used to trip any dialer UL listed for Central Station/Remote Station
Services. The UDACT-F may also be used. Refer to Figure 2-11, “UDACT-F Mounting to MS-9200,” on page 30
and Figure 2-12, “External UDACT-F Mounting in ABS-8RF,” on page 31, for information on installation.
Notes:
1.
Reference the MS-5012 Manual for additional information
2.
Program the MS-5012 for slave operation
3.
SW2 Trouble switch located on the bottom right of the MS-9200 main circuit board, must be positioned in the
down position for this application. This prevents the transmission of a trouble on the loss of AC power
TABLE E-1:
MS-5012 Connections to MS-9200
MS-5012
MS-9200
Alarm
TB2-1
TB3-5
TB2-2
TB3-3
Trouble
TB2-3
TB3-8
TB2-4
TB3-6
Supervisory
TB2-9
TB3-2
TB2-10
TB3-1
24V UNREG 24V NONRS 24V RST
BELL 2 POWER
BELL 1 POWER
SUPV
ALARM
TROUBLE
PC/PRINTER TERM COMM
+ - + - + -
B+ A+ A- B-
B+ A+ A- B-
NO C NO NC C NO NC C
A B B+ A+ B- A-
1 COMM 2
ACS
SHIELD
SLC
SLC
OUT+ IN+ OUT- IN-
T
B
4
T
B
2
T
B
1
T
B
3
T
B
7
T
B
5
T
B
6
FIGURE E-1:
Central Station Service Using MS-5012
ELR = 2.2K ohms (supplied with MS-5012)
AC wiring for DACT/FACP must be
connected to the same branch circuit.
MS-9200
MS-5012
Phone Line
Transformer
Alarm
Trouble
Supv.