Document #51003 Rev.E 01/11/02 P/N 51003:E
27
UL Power-limited Wiring Requirements
2.6
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all
power-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different
knockouts and/or conduits. A typical wiring diagram for the MS-9200 is shown in Figure 2-7.
24V UNREG 24V NONRS 24V RST
BELL 2 POWER
BELL 1 POWER
SUPV
ALARM
TROUBLE
PC/PRINTER TERM COMM
G
N
D F
A
UL
T
D
IS
ABL
E
T
R
AN
SF
O
R
M
E
R
1
TR
A
N
S
F
O
R
M
E
R
2
- +
BATTERY
RS
-2
32
PC
/P
R
IN
T
E
R
RS
-4
8
5
TE
R
M
. M
O
D
E
TR
OU
B
LE
+ - + - + -
B+ A+ A- B-
B+ A+ A- B-
NO C NO NC C NO NC C
A B B+ A+ B- A-
1 COMM 2
ACS
SHIELD
SLC
SLC
OUT+ IN+ OUT- IN-
T
B
4
T
B
2
T
B
1
T
B
3
T
B
7
T
B
5
T
B
6
J16
J6
JP3
JP1
CAUTION
HIGH VOLTAGE
J3
TB8
J19
J17
JP4
SW1
SW3
SW2
CA
UT
IO
N!
HIG
H
V
O
L
TAG
E
GNDFAULT
C
C
C
C
C
C
C
C
NC
NC
NC
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
NO
NO
NO
FIGURE 2-7:
Typical UL Power-limited Wiring Requirements
Power-limited Circuits
Power-limited Circuits
Nonpower-limited Circuits
Power-limited Circuits
Nonpower-limited Circuits
AC Power
Note: Output is nonpower-
limited only if programmed
as municipal box output.
Power-limited Circuit
Nonpower-limited Circuit
Nonpower-limited Circuit
No connection
Power-limited Circuit
Power-limited Circuit
Power-limited Circuit
Nonpower-limited Circuit
Nonpower-limited Circuit
Nonpower-limited Circuit
RTM-8F UL Power-limited Wiring Requirements
Nonpower-limited and power-limited wiring must have a
minimum distance of 0.25" wire-to-wire. If this module is used to
drive nonpower-limited and power-limited circuits, follow the
instructions below:
1.
Skip a set of dry contacts to maintain the 0.25" required
space between power-limited and nonpower-limited
circuits.
2.
If this module is needed to drive power-limited and
nonpower-limited relays that are next to each other, make
no connection to the Normally Open contact which sepa-
rates the two groups of relays. Refer to the typical wiring
diagram to the right.
Refer to Figure 2-16, “RTM-8F Relay Transmitter Module,” on
page 34, for additional information on the RTM-8F.
Grounding Stud
9200pwr
l.c
dr