Appendix B: NFPA Standard-Specific Requirements
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
38
MS-4412B/MS-4424B Instruction Manual PN 15125:G1 10/22/02
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
Note:
This application is not FM approved
Using the Noti-Fire 911AC DACT for connection to a Central Station Receiver or Protected Premises
Receiving Unit.
• AC Wiring for DACT/FACP must be connected to the same circuit.
• If the unit is not mounted in the control panel’s backbox all connections must be in conduit, less
than 20 ft. (609.6 cm) in length in the same room.
• For additional information refer to the Noti-Fire 911AC Instruction manual.
Figure 23 DACT Connections
+
–
TB3
TB4
OPT1
IN #2
B+ B–
IN #3
B+ B–
IN #4
B+ B–
SUPV 1 SUPV 2
JP1
TB1
LATCH
DISABLE
J2
STD DACT
MS44
B-91
1a
c.cd
r
Place jumper over pins as shown when employing
a DACT. This directs the control panel to transmit
all trouble conditions except AC LOSS.
To Central
Station
PS 1270
12Volt
7AH Battery
To AC Power
See Below for Terminal
Connections
Control Panel
To Common
Terminal of Relay
Jumper
4XZMF Zone
Relay Module