2. Installation
Optional Modules
24
MS-4412B/MS-4424B Instruction Manual PN 15125:G1 10/22/02
Setup and Configuration
Transmitter Module - 4XTMF (4412TM)
Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module
as shown below. Polarities shown in activated positions.
Note:
Dummy load terminals 6 and 7 (4.7K [2.2K for 12V], 1/4 W resistor) if Municipal Box is not connected.
Note:
Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.
Pushing the Disconnect Switch down will prevent unwanted activation of the Municipal Box during testing
of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is
disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the
Municipal Box.
Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring
Requirements" on page 16.
Figure 14 Transmitter Module Configuration
TB1
TBL
J1
J2
4XTMF
.cd
r
TBL Jumper
Disconnect Switch
Disconnect LED
Remote Alarm (Power-limited)
Remote Trouble (Power-limited)
Municipal Box (Nonpower-limited)
No Connection
+
–
+
–
+
–