2. Installation
Power-limited Wiring Requirements
16
MS-4412B/MS-4424B Instruction Manual PN 15125:G1 10/22/02
24 Volt Connections
Connect the battery cable (p/n 75202) to terminal J9 on the main circuit board using the plug-in connector
provided. Connect red wire to positive (+) terminal and black wire to negative (–) terminal on opposing
batteries. Do NOT connect battery interconnect wire at this time.
12 Volt Connections
Connect the battery cable (p/n 75202) to terminal J9 on the main circuit board using the plug-in connector
provided. The short cable (battery interconnect) may be removed from bundle. Do NOT connect cables
to battery at this time.
Figure 4 Battery Installation and Connection
Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-
limited circuit wiring must remain at least 0.25 in (6.35 mm) away from any nonpower-limited circuit
wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must pass
through separate knockouts and/or conduits.
Figure 5 Power-limited Wiring Requirements
J9
TB1
J9
TB1
MS
44
B-
BA
Tc
on
n.cd
r
24 Volt
Connections
12 Volt
Connections
TONE
SILENCE
ALARM
SILENCE
ALARM
ACTIVATE
SYSTEM
RESET
AC POWER
SYSTEM
ALARM
ALARM TEST
SUPERVISORY
SYSTEM
TROUBLE
CIRCUIT
TROUBLE
ALARM
SILENCED
POWER
TROUBLE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
SW1
TB2
TB3
TB4
OPT1
OPT2
J9
J1
JP12
TB1
OUT#1
B+ B–
OUT#2
B+ B–
ALARM
NO NC C
IN #2
B+ B–
IN #3
B+ B–
IN #4
B+ B–
SU PV 1 SU PV 2
JP1
TB1
LATCH
DISABLE
J2
Power-limited
Circuit
Nonpower-limited
Circuit
All upper terminals are power-limited circuits
Power-limited
Circuit
M
S
44B
-p
lw
ir
ing
.cdr