1. Product Description
DIP Switch Functions
10
MS-4412B/MS-4424B Instruction Manual PN 15125:G1 10/22/02
DIP Switch Functions
The table below describes the DIP switch functions. For a more detailed explaination see "Setting Mode
of Operation" on page 27.
Options
Three optional modules are available for use on the control panel. The control panel provides mounting
slots for two of these optional module boards.
Transmitter Module - 4XTMF (12V: 4412TM)
The Transmitter Module provides a supervised output for a Local Energy
Municipal Box transmitter and alarm and trouble reverse polarity circuits for
Remote Station Service. Also included is a DISABLE switch and disable
trouble LED.
Note:
As a jumper option, the alarm reverse polarity circuit will open on trouble if no
alarm exists.
Specifications for Local Energy Municipal Box service
(NFPA 72 Auxiliary
Fire Alarm System)
Supervisory current: 5.0 mA.
Trip current: 0.35 amps (subtracted from Notification Appliance power).
Coil Voltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms.
Municipal Box wiring can leave the building.
Specifications for Remote Station Service
(NFPA 72 Remote Station Fire Alarm System)
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 12 or 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.
#1
Alarm
Verification
ON Alarm Verification enabled (two-minute period).
OFF No verification employed.
#2
Waterflow
ON Zone 3 configured for Waterflow.
OFF Zone 3 functions as a normal Initiating Device Circuit.
#3
Supervisory
ON Zone 4 configured for Supervisory.
OFF Zone 4 functions as a normal Initiating Device Circuit.
#4
Silence
Inhibit
ON Alarm Silence will not function for 60 seconds after initiation of an alarm.
OFF Alarm Silence is possible at any time after initiation of an alarm.
#5
Disable
NACs
ON Two Notification Appliance Circuits and the Alarm Relay are disabled.
OFF Two Notification Appliance Circuits and the Alarm Relay are enabled.
#6
Walk Test
ON Places the panel into Walk Test Mode.
OFF Normal Operating Mode.
Note:
See “Setting Mode of Operation” on page 27 for a more detailed explanation of DIP switch functions.