Universal Digital Alarm Communicator - 411UDAC
Appendix B: NFPA Standard-Specific Requirements
MS-4412B/MS-4424B Instruction Manual PN 15125:G1 10/22/02
39
Universal Digital Alarm Communicator - 411UDAC
The following figure illustrates an example of Central Station/Remote Station Receiver or Protected
Premises Receiving Unit reporting using a 411UDAC. The relay contacts of the MS-4412B/MS-4424B
may be used to trip any dialer listed for Central Station/Remote Station services. For additional information
refer to the Instruction Manual for the 411UDAC.
• All connections between the control panel and the 411UDAC must be in conduit, less than 20 feet
(6.1 meters) in length in the same room.
• Any zone of the 411UDAC can be wired to function as alarm, trouble or supervisory; the unit must
be programmed accordingly. In this example, Zone 1 is wired to the control panel’s alarm relay,
Zone2 is wired to the control panel’s trouble relay, and Zone 3 is wired to the optional module’s
supervisory relay.
• AC power is supplied directly to the 411UDAC, not through the control panel. AC wiring for both
the 411UDAC and the control panel must be connected to the same AC branch circuit.
• End-of-line Resistors must terminate all circuits. In this example, Zone 4 is unused and is terminated
at the board.
• When employing a DACT, place the JP1 jumper, on the control panel, as shown below. This directs
the panel to transmit all trouble conditions except AC LOSS. The DACT must be configured to
transmit AC power loss to the central station.
Figure 24 411UDAC Connections
TB4
OPT1
IN #2
B+ B–
IN #3
B+ B–
IN #4
B+ B–
SUPV 1 SUPV 2
JP1
T B1
LAT CH
DIS ABLE
J2
STD DACT
TB2
TB4
TB1
RELAY 1
NO NC C
RELAY 2
NO NC C
NAC
B+ B-
ZONE 1
B+ B-
ZONE 4
B+ B-
ZONE 2
B+ B-
ZONE 3
B+ A+ A- B-
+12V PWR
+ -
PH1
PH2
Trouble
Alarm
Secondary Phone Line
Primary Phone Line
Modular Cable
P/N MCBL-6
Super-
visory
Control Panel
4XZMF Zone
Relay Module
MS4
4
B
-4
11.cd
r
Jumper
Zone 1
Zone 2
Zone 3