ALARM LIST
5
18
WATER PUMP OUT NOT CONNECTED
(the output for the water pump control is not connected)
19
WATER PUMP OUT SHORT TO GND
(the output for the water pump control is short circuited to ground)
20
ADDITIVE PUMP OUT NOT CONNECTED
(the output for the additive pump control is not connected)
21
ADDITIVE PUMP OUT SHORT TO GND
(the output for the additive pump control is short circuited to ground)
Codice Descrizione
Soluzione
allarme
CHECK THE WIRING CON-
NECTION
• check the connection
• if the problem persists, replace
the actuator (relay or other)
• if the problem persists, replace
the device