4.6 LEVEL 2 - Sensor input E2
After power ON, the display switches to the "Amplitude" root display.
From here, the 6 key (press 3x) can be used to change to level 2. The following parameters are
available:
A logical 1 causes a reaction.
A logical 0 causes no reaction.
Parameter: F1 [function]
Code A and B
Value can be set to O, S
O – An applied HI signal is not inverted and is
further
processed
as
logical
1.
An applied LO signal is not inverted and is
further
processed
as
logical
0.
S – An applied HI signal is inverted and is
further
processed
as
logical
0.
An applied LO signal is inverted and is
further
processed
as
logical
1.
Parameter: Dropout delay S1 [s]
Code A and B
Value can be set from 0.0 - 99.9
Increment 0.1 s
There is a logical result, depending on the inversion.
If the logical result is 1, the output is switched off with a delay
by
the
time
S1.
Parameter: Pick-up delay S2 [s]
Code A and B
Value can be set from 0.0 - 99.9
Increment 0.1 s
There is a logical result, depending on the inversion.
If the logical result is 0, the output is switched on with a delay
by
the
time
S2.
Parameter: Debouncing time S [ms]
Code A and B
Value can be set from 0.1 - 99.9
Increment 0.1 ms
If level changes occur very quickly in succession,
double pulses can be hidden via the debouncing time.