Operating instructions FS-26E
Status as of 10 / 2019
Page 20
Display of the program version
Error number is displayed.
Value of applied analog voltage [V=]
or
Value of the applied analog current [mA=]
or
Value of the current acceleration [g]
Depending on the programmed setpoint specification (parameter AE), the
applied
analog
value
is
displayed
here.
4.5 LEVEL 1 - Enable input E1
After power ON, the display switches to the "Amplitude" root display.
From here, the 6 key (press 2x) can be used to change to level 1. The following parameters are
available:
A logical 1 causes a reaction.
A logical 0 causes no reaction.
Parameter: F1 [function]
Code A and B
Value can be set to O, S
O – An applied HI signal is not inverted and is
further
processed
as
logical
1.
An applied LO signal is not inverted and is
further
processed
as
logical
0.
S – An applied HI signal is inverted and is
further
processed
as
logical
0.
An applied LO signal is inverted and is
further
processed
as
logical
1.
Parameter: Debouncing time S [ms]
Code A and B
Value can be set from 0.1 - 99.9
Increment 0.1 ms
If level changes occur very quickly in succession,
double pulses can be hidden via the debouncing time.
Via input E1, all outputs are switched off or enabled with higher priority over the
programmed logic in the outputs.