Mapping Overview
Programming Overview
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
75
.
8.2 Mapping Overview
This Section of the Manual describes an overview of the mapping.
The Mapping is an important concept used with the control panel. In general terms, the mapping is assigning or linking events
to outputs that will activate when the events occur. To do this, assign the input points to the input zones, output points to the
output groups and then link or map the zones and the output groups.
Figure 8.1 is a brief overview of the concept of mapping. The next several pages of the manual show these subjects in detail.
Figure 8.1 Mapping Overview Diagram
8.2.1 Input Point Mapping
The Input Points are assigned to the Input Zones. Any input point can be assigned to any input zone. (Input points can be
assigned to one zone only. An input point can be designated as “Unused,” which means it has not been assigned to a zone).
1- Review System
Press 1 if you need to review the JumpStart configuration. The Review System Menu will appear.
Press 1 to review the Entire System or press 2 for Changes Only.
2- Repeat JumpStart
Press 2 if you need to rerun the JumpStart for any reason.
3- Accept Configuration
1.
If you are ready to make the JumpStart configuration permanent, select 3.
2.
The System will prompt you if the installation contains any addressable duct detectors used. If there
are no duct detectors, select 2 for No and skip to Step 8.
If the System contains duct detectors, select 1 for Yes and continue with Step 3.
3.
From the list that displays, select the SLC that contains the duct detectors.
4.
The first photoelectric or ionization detector on the System will display.
Select 1 for DUCT and 2 for NonDUCT.
5.
Press the up arrow to select the next detector. Select 1 for the DUCT and 2 for the NonDUCT.
Continue until all the duct detectors have been selected. (Note: You can move backwards through the
list with down arrow).
6.
When you reach the last detector on this device, press the left arrow.
7.
The System will prompt you if there are any duct detectors used. If there are, select 1 for Yes and the
message will prompt, Have All Addressable Duct Detectors Been Identified? Left arrow for “No”,
Right arrow for “Yes”. If there are no more duct detectors, continue with Step 8.
8.
The System will restart with the saved JumpStart configuration.
9.
After the System resets, it will use the new JumpStart configuration.
4 - Discard Changes
If you want to discard the changes, and keep the previous configuration you had before running this
JumpStart, press 4.
Table 8.1 JumpStart Chart