Model FCP-300 Basic Operating Instructions
These Instructions must be framed and displayed next to the FCP-300 panel in accor-
dance with the NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the Sys-
tem in accordance to NFPA 72.
Operation
Task to Perform
Silence Alarms and Troubles Press SILENCE, then enter a code if prompted. The Silence LED will light.
Reset Alarms
Press RESET, then enter a code if prompted.
View Alarms, Supervisories,
and Troubles
For each type of condition, press the Up or Down button associated for the Alarms, Supervisories, or
Troubles.
View Status of Point
1. Press ENTER to access the Main Menu.
2. Press 2 to select the Point Functions.
3. Then press 2 to select the Point Status.
4. Select the module the device is located on by using the Up or Down button. Then press ENTER.
5. Enter the point number.
Conduct a Fire Drill
1. Press ENTER to access the Main Menu.
2. Then Press 1 to select the System Tests.
3. Press 1 to select the Fire Drill.
4. Press ENTER to start the fire drill.
5. Press ENTER to end the fire drill.
Check Detector Sensitivity
1. Press ENTER to access the Main Menu.
2. Press 2 for the Point Status.
3. From the list that displays, select the SLC module where the point you want to view is located.
4. The fourth line of the display shows the Sensitivity Status.
“NORMAL” means the detector is in compliance with NFPA 72.
“CAL MAINT” means the detector is in compliance with NFPA 72, but maintenance should be
performed soon.
“CAL TRBLE” means the detector is not in compliance with NFPA 72.
Set Time and Date
1. Press ENTER to access the Main Menu.
2. Press 4 to select Set Time & Date. Enter a code if prompted.
3. Make changes in the fields on the screen as necessary.
4. When the time and date are correct, press ENTER.
Enable / Disable a Point
1. Press ENTER to access the Main Menu.
2. Press 2 to select the Point Functions.
3. Press 1 for Disable / Enable Pt.
4. Press 7 for Disable / Enable Pt.
5. Use the Up or Down button to move through the list. Then, press ENTER to select the module
where the point you want to disable/enable is located.
6. Enter the point or circuit number that you want to disable/enable.
7. Press the right arrow key to toggle between NORMAL (enable) or DISABLE.
View Event History
1. From the Program Menu.
2. Press 3 to select the Event History.
3. Press the Up or Downbutton to view events in the History buffer.
For Service Call:
P/N LS10162-002FK-ERev A ECN: 2890
FIRE:
CO:
EMERGENCY:
SYSTEM:
ALARM SUPERVISORY TROUBLE
ALARM SUPERVISORY
ALARM SUPERVISORY
TROUBLE