122
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
System Operation
Releasing Operations
Figure 10.6 Wiring Configuration for Solenoid
10.7.1 Single Interlock Zone Releasing
A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch.
Conditions Required for an Interlock Release Alert Output Activation
If any single addressable detector is activated, the “Interlock Release Alert” output will activate. This alerts the user that the
initial stages required for a release condition are present. (Also refer to Table 10.6).
Conditions required for a Detector Alarm and Interlock Release Alarm Output
Manufacturer
Part Number
Rated Voltage, DC
Rated Current,
Milliamp
Asco
T8210A107
24 VDC
700
8210G207
24 VDC
442
HV2740607
24 VDC
375
HV2838521
24 VDC
375
HV2740608
24 VDC
375
Honeywell/Skinner
701X7028
24 VDC
917
Barnbrook System
EA45
24 VDC
200
Kidde Fenwal
890181
24 VDC
2000
486500
24 VDC
290
895630
24 VDC
2000
897494
24 VDC
1500
Minimax
88 7363
24 VDC
1040
88 5738
24 VDC
1040
88 9323
24 VDC
500
Nohmi Bosai
R85M10
24 VDC
1200
Parker Hannifin
70610006
24 VDC
417
10610707
24 VDC
417
Snap-tite
2823A-2NB-A4F6
24 VDC
458
2823A-2NB-A4F5
12 VDC
917
TLX
PA0036-A
24 VDC
600
Versa Valves
CGS-4232-NB3-S2
24 VDC
438
Victaulic
753E
24 VDC
364
767
24 VDC
364
Viking
11591
24 VDC
417
11595
24 VDC
417
11592NC
24 VDC
416
16360
24VDC
500
Table 10.5 Approved Releasing Solenoids
!
WARNING:
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.