FCP-300/FCP-300ECS Manual — 

P/N LS10145-002FK-E:A  3/12/2021

Control Panel Installation

FIK-RA1000 Remote Annunciator Installation

4.6.1  Mounting the FIK-RA1000

This Section of the Manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted. 

Figure 4.17 shows the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages   

Figure 4.17  Annunciator Parts

The FIK-RA1000 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunci-

ator, use a 5/64 hex wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4.18 for loca-
tion of the set screws.)         

Figure 4.18  Annunciator Back Box and Bezel Details

Flush Mounting

This Section of the manual describes flush mounting. You can flush-mount with or without an electrical box. 

Summary of Contents for FCP-300

Page 1: ...A P N LS10145 002FK E A ECN 151526 Document LS10145 002FK E 3 12 2021 Addressable Fire Alarm Control Panel FCP 300 FCP 300ECS Installation Operation Manual ...

Page 2: ...r reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qualified fire protection specialist Heat detectors are designed to protect property not life IMPORTANT Smoke detectors must be installed in the same room as the control panel and in rooms ...

Page 3: ...s prior to any drilling filing ream ing or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty w...

Page 4: ...h any questions about software and the appropriate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic ...

Page 5: ... 19 3 7 1 Current Draw Worksheet Requirements 19 3 7 2 Current Draw Worksheet for FIK SLC Devices 20 3 7 3 Maximum Battery Standby Load 23 Section 4 Control Panel Installation 24 4 1 Mounting the Control Panel Cabinet 24 4 1 1 Preventing Water Damage 24 4 1 2 Removing the FCP 300 ECS Assembly from the Housing 24 4 1 3 Ethernet Connection 24 4 2 AC Connection 25 4 3 Battery Power 25 4 3 1 RBB Acces...

Page 6: ...iring Options 56 5 3 1 Fiber Loop Modules 56 5 3 2 FIK NIC Installation 58 5 4 Setting the Network ID for each Panel 60 Section 6 Network Management 61 6 1 Network Diagnostics 61 6 1 1 Ping Panel 61 6 1 2 Data Network Status 61 6 1 3 Voice Network Status 61 6 2 Network Programming 61 6 2 1 Learn Network 61 6 2 2 Edit Network Names 61 6 2 3 Edit Panel ID 61 6 2 4 Computer Access 62 6 2 5 Access Cod...

Page 7: ...it OPG Template 97 9 5 Point 98 9 5 1 Point Programming For FIK 6815 Module 98 9 5 2 Point Programming for the Internal or the External Power Module FIK RPS1000 100 9 5 3 Point Programming For FIK 5880 or 5865 Modules 101 9 5 4 Point Programming for FIK 5496 102 9 5 5 Point Programming for FIK AMP 102 9 5 6 Point Programming for FIK NVCM and FIK RVM Modules 103 9 6 System Options 105 9 6 1 Communi...

Page 8: ...9 1 Recording an F Key Macro 124 10 9 2 Aborting an F Key Macro Recording Session 124 10 9 3 Erasing an F Key Macro 124 10 9 4 Using a Recorded F Key Macro 124 10 9 5 F Key Status Event 124 10 9 6 F Key Map Inhibit 124 Section 11 Emergency Communication System Operation 125 11 1 Overview 125 11 2 LOC Functionality 125 11 2 1 Keys and LEDs 125 11 2 2 Gaining ECS Control 126 11 2 3 Manual ECS 126 11...

Page 9: ...Multiple Device Locator 146 13 3 3 I O Point Control 147 13 3 4 Earth Fault Resistance 147 Section 14 Installation Records 148 14 1 Detector and Module Point Record 148 14 2 Conventional Output Point Record 150 Appendix A Compatible Devices 151 A 1 Notification Appliances 151 A 1 1 Two Wire Detectors 158 A 2 Four Wire Smoke Detectors Devices UL Listed 159 A 3 Door Holders UL Listed 161 A 4 Relays ...

Page 10: ...ately Can be used with Models FIK 5865 3 FIK 5865 4 and FIK 5880 in any combination for a total of eight devices on one control panel See Sections 4 11 and Section 4 12 for additional information on these models Printing of the Event Log is available through the Model FIK 5824 Serial Parallel Printer Interface Module 250 software zones and 250 output groups Add six Flexput circuits with each FIK R...

Page 11: ...mbination of 32 panels of these model numbers FCP 75 FCP 300 FCP 300ECS FCP 2100 or FCP 2100ECS SWIFT Smart Wireless Integrated Fire Technology Table 1 1 Terminology Type of Device Model Description FIKE Addressable SLC Devices See Section 7 1 for a list of compatible devices SWIFT Wireless SLC Devices See Section 7 4 for a list of compatible devices Other Modules FIK 5824 Serial Parallel Printer ...

Page 12: ...lectric smoke detector with thermal 135 F with 4 base FIK W HEAT ROR Wireless Heat Rate of Rise Detector 135 fixed with 4 base FIK W HEAT Wireless Heat 135 fixed Heat Detector with 4 base FIK W MONITOR Wireless Addressable Monitor module FIK W RELAY Wireless Addressable Relay module B210W 6 wireless base FIK W WGI Wireless Gateway Refer to the SWIFT wireless Installation Manual P N LS10036 FK E fo...

Page 13: ...3453 Fike or www fike com If the equipment is causing harm to the telephone network the Telephone Company may request that you disconnect the FCP 300 until the problem is resolved This product cannot be adjusted or repaired in the field It must be returned to the factory for service This equipment is not designed for use with party line service The connection to the party line service is subject t...

Page 14: ...not be used When two count is used the detector spacing shall be cut in half You shall not use the alarm verification feature and no delay shall be used P A S Positive Alarm Sequence feature shall be used only with automatic detectors 2 2 2 Central Station Fire Alarm Systems Requirements 1 Use both phone lines Enable phone line monitors for both lines 2 You must program a phone number and a test t...

Page 15: ...WHV 125W Amp1 O O O O Y Y FIK INT50W Internal 50W1 Amp O O O O Y Y FIK SW24 Switch annunciator O O O O O Y FIK CE4 Speaker expander mod3 O O O O O O FIK 6815 SLC Expander O O O O O O FIK NVCM Network Voice Card O O O O O O FIK NIC Network Card O O O O O O FIK FML FIK FSL Fiber Module O O O O O O Y YES N NO O OPTIONAL 1 A maximum of eight 50 125 Watts Amplifiers for a maximum of 1000 Watts per the ...

Page 16: ...3 Software Downloads In order to supply the latest features and functionality in the fire alarm and the life safety technology to our customers we make frequent upgrades to the embedded software in our products To ensure that you install and program the latest features we strongly recommend that you download the most current version of software for each product prior to commissioning any System Co...

Page 17: ...e shield beads or by wrapping it around a ferrite toroid Terminal Block 6 TROUBLE NC Normally closed relay contact 24 VDC 2 5 A resistive COM Common terminal NO Normally open relay contact RELAY 1 NC Normally closed relay contact 24 VDC 2 5 A resistive COM Common terminal NO Normally open relay contact RELAY 2 NC Normally closed relay contact 24 VDC 2 5 A resistive COM Common terminal NO Normally ...

Page 18: ...Outputs SBUS Devices Phone Lines SLC IN OUT AC Power Input Note 1 4 spacing must be maintained between each of these circuit types as well as between power limited and non power limited circuits SLC Phone Lines AC Power Input SBUS Devices In Out Relay Outputs NAC Aux Power Outputs Battery Battery Note 1 4 spacing must be maintained between each of these circuit types and between the power limited ...

Page 19: ...tandby battery requirements 1 Use the Current Draw Worksheet to determine the current draw and the standby battery requirements Use Table 3 3 if you install the FIK SLC Devices to determine the current draw For the FCP 300 the worst case current draw is listed for the panel addressable devices and all SBUS expanders Fill in the number of addressable devices that will be used in the System and comp...

Page 20: ...current requirements during thalarm battery standby operation when the SLC devices are installed TheFCP 300FACP supports up to a total of 300 SLC devices consisting of any combination of Sensors and Mod ules 7 Device Number of Devices Current per Device Standby Current Alarm Current For each device use this formula This column X This column Current per number of devices Fire Panel Current draw fro...

Page 21: ...V WH intelligent Sounder Base Aux Pwr Standby 5mA mA Alarm high vol 35mA mA SLC Standby 3mA mA B200SR LF IV WH Low Frequency Sounder Base Aux Pwr Standby 1mA mA Alarm 125mA mA B200S LF IV WH Low Frequency Sounder Base Aux Pwr Standby 55mA mA Alarm high vol 140mA mA SLC Standby 30mA mA B224RB IV WH Relay Base Standby Alarm 5mA mA mA RTS151 151 KEY Alarm 7 5 mA mA RA100Z Alarm 10 mA mA SLC Isolator ...

Page 22: ...h without FIK CE4 8 max Standby 10 mA mA Alarm 10 mA mA FIK DUAL50W 8 max Standby Alarm 10 mA mA mA FIK 50WBU 8 max Standby Alarm 10 mA mA mA FIK INT50W Internal Amplifier 8 max Standby 52 mA mA Alarm 25V 275 mA mA Alarm 70V 310 mA mA FIK NVCM Network Voice Control Module 1 max Standby Alarm 59 mA mA mA FIK SW24 Switch Expander 8 max Standby 10 mA mA Alarm 25 mA mA FIK RPU Remote Paging Unit 7 max...

Page 23: ...Standby 5 mins Alarm 24 hr Standby 15 min alarm 24 hr Standby 20 min alarm 17AH 535mA 473mA 442mA 18AH 569mA 506mA 475mA 24AH 769 mA 706mA 675mA 33AH 1 07A 1 01A 975mA 35AH 1 14A 1 07A 1 04A 40AH 1 30A 1 24A 1 21A 55AH 1 80A 1 74A 1 71A Table 3 4 Maximum Battery Standby Loads for 24 Hour Standby Rechargeable Battery Size 90 hr Standby 5 min alarm 90 hr Standby 15 min alarm 90 hr Standby 20 min ala...

Page 24: ...the top edge or the bottom edge to the exterior side of the sheet rock Do NOT flush mount in a wall designated as a fire break Figure 4 1 FACP Cabinet Base 4 1 1 Preventing Water Damage The water damage to the fire System can be caused by moisture entering the cabinet through the conduits Conduits that are installed to enter the top of the cabinet are most likely to cause the water problems Instal...

Page 25: ...ed in an RBB see Section 4 3 1 for details Use 12V batteries of the same AH rating Determine the correct AH rating as per your current load calculation see Section 3 7 Wire batteries in series in sequence to produce a 24 volt equivalent Do not parallel batteries to increase the AH rating It is recommended that you replace batteries every five years Figure 4 3 Battery Connection WARNING RISK OF ELE...

Page 26: ... be mounted onto 3 4 inch plywood This is necessary because the weight of the batteries inside the accessory cabinet could cause the cabinet to pull away from the drywall When mounting the cabinet on concrete especially when moisture is expected attach a piece of 3 4 inch plywood to the concrete surface and then attach the RBB cabinet to the plywood If you use the battery cable extenders provided ...

Page 27: ...ed to calculate the loads for each SBUS to ensure that each SBUS does not exceed 1 0A To calculate the wire gauge that must be used to connect SBUS modules to the control panel it is necessary to calculate the total worst case current draw for all modules on a single 4 conductor bus The total worst case current draw is calculated by adding the individual worst case currents for each module The ind...

Page 28: ... 010 amps FIK NVCM with FIK SW24 115 amps 185 amps FIK NVCM Network Voice Control Module 059 amps FIK EMG FIK NVCM keypad 06 amps FIK LOC 210 amps 325 amps FIK DUAL50W 010 amps FIK DUAL50W WITH FIK 50WBU 010 amps FIK NIC Network Interface Card 021 amps Table 4 1 SBUS Device Current Draw NOTE Refer to Table 3 2 if using FIKE SLC devices to determine the maximum number of each type of device that ca...

Page 29: ...le it can be found that the available options are as follows 4 4 2 Wiring Configurations Figure 4 8 illustrates the SBUS Class B configuration Figure 4 8 SBUS Class B Wiring Current Draw Amps Amps FIK RA1000 Current Draw 2 x 100 amps 200 amps FIK 5496 Current Draw 1 x 010 amps 010 amps FIK 5865 Current Draw 1 x 200 amps 200 amps FIK 5824 Current Draw 1 x 040 amps 040 amps Total Worst Case Current ...

Page 30: ...A100 see Section 4 12 1 5 The new FIK RA100 module must be added to the System through programming JumpStart will add the module automatically see Section 8 1 You can also add it manually see Section 9 2 2 6 Select a name if desired See Editing Module ID on page 121 4 5 1 Mounting the FIK RA100 This Section of the manual describes the procedure to mount the remote annunciator The annunciator can b...

Page 31: ...to the main control panel See Figure 4 8 9 Attach the annunciator and door assembly to back box as shown in Figure 4 12 using the supplied screws Figure 4 12 Attaching Annunciator Door Assembly to Backbox Surface Mounting The optional Model FIK RA100TR Trim Ring Kit is available for use when surface mounting 1 Remove the desired knock out See Figure 4 11 Wire Knockouts Wire Knockouts Wire Knockout...

Page 32: ...e rest of the mounting screws Figure 4 13 Back Box Surface Mount Holes 3 Run wires to the control panel 4 Place the trim ring over the back box as shown in Figure 4 14 Figure 4 14 Trim Ring Installation 5 Attach the Door assembly to the back box using screws provided 6 After the annunciator wiring to the panel has been completed described in Section Figure 4 5 replace the electronic assembly in th...

Page 33: ...dded to the FCP 300 ECS System Figure 4 16 Model FIK RA1000 Remote Annunciator Front View The FIK RA1000 installation involves the following steps 1 Make sure power is off at the panel 2 Mount the FIK RA1000 in the desired location see Section Figure 4 6 1 3 Connect the FIK RA1000 to the panel see Section Figure 4 6 2 4 Use the DIP switches on the back of the FIK RA1000 to assign an ID to the FIK ...

Page 34: ...tions for disassembling and mounting appear on the following pages Figure 4 17 Annunciator Parts The FIK RA1000 comes from the factory fully assembled You must disassemble it for mounting To disassemble the annunci ator use a 5 64 hex wrench to remove the set screws located on the bottom of the annunciator bezel See Figure 4 18 for loca tion of the set screws Figure 4 18 Annunciator Back Box and B...

Page 35: ...nted Figure 4 20 Model FIK RA2000 Remote Annunciator Front View The FIK RA2000 installation involves the following steps 1 Make sure the power is off at the panel 2 Mount the FIK RA2000 in the desired location see Section 4 7 1 3 Connect the FIK RA2000 to the panel see Section 4 7 2 4 Use the DIP switches on the back of the FIK RA2000 to assign an SBUS ID to the FIK RA2000 5 The FIK RA2000 module ...

Page 36: ...teps to flush mount the FIK RA2000 1 The back box dimensions are 9 W x 8 3 8 H The minimum depth required is 2 The back box can be mounted prior to the complete installation of the FIK RA2000 using any of the mounting holes shown in Figure 4 10 Figure 4 21 Back Box Mounting Holes 2 Remove knockout holes as needed for wires See Figure 4 11 for backbox knockout locations Figure 4 22 Back Box Knockou...

Page 37: ...unting The Model FIK RA100TR Red Trim Ring Kit is available for use when surface mounting the FIK RA2000 1 Remove the desired knock out See Figure 4 11 2 To properly mount the back box insert a single screw into the key shaped mounting hole Do not tighten all the way See Figure 4 13 Place a level on top of the back box with the back box level insert the rest of the mounting screws Figure 4 24 Back...

Page 38: ... additional addressable devices The maximum number of SLC devices per panel is 300 The number of FIK 6815 s is limited by the maximum number of SBUS devices To install the FIK 6815 do the following 1 Make sure the power is off at the panel 2 Mount the FIK 6815 in the FCP 300 ECS cabinet or the FIK RPS1000 cabinet 3 Use the standoffs located under the control panel board assembly and secure it with...

Page 39: ...ystem The programming steps are described in Section 9 2 2 Figure 4 28 FIK 6815 Connection to Main Panel Assembly 4 9 FIK 5824 Serial Parallel Interface Module Installation The FIK 5824 Serial Parallel Printer Interface Module allows you to connect a printer to the panel so you can print a real time log of the System Events The procedure to install the FIK 5824 appear below The FIK 5824 and the pr...

Page 40: ...inter is used for ancillary only 1 From the Main Menu select 7 for Program Menu 2 Select 1 for Module 3 Select 1 for Edit Module 4 From the list that displays select the FIK 5824 Module you want to configure 5 Press ENTER to bypass the next two screens A screen similar to the one shown in Figure 4 30 will display Figure 4 30 Selecting the Printer and the Output Port Options 6 Select the Printer an...

Page 41: ... FIK 5880 also has eight inputs to used for dry contact monitoring The following sub sections describe the hardware installation For additional programming information refer to Section 9 4 10 1 FIK 5880 Board Layout Figure 4 31 illustrates the FIK 5880 board showing the locations of the screw terminals to be used for the connections to the following items Figure 4 31 FIK 5880 Board Layout panel an...

Page 42: ... gets its power from Pin 11 The Internal resistors are sized so that there is approximately 10 mA of current for each LED no series resistors are required The LED outputs can be mapped to the output circuits For programming information refer to Section 9 Wire the LEDs as shown in Figure 4 33 On the Connector P1 Pin 12 is a common open collector output used to controll a PZT If used the FIK 5880 PZ...

Page 43: ...FIK 5865 3 and FIK 5865 4 are LED annunciators The FIK 5865 4 has 30 mappable LEDs remote silence and reset key switches and a general System trouble LED The FIK 5865 3 has 30 mappable LEDs only These LEDs are arranged as 15 pairs of red typically used for the alarm and yellow typically used for the trouble LEDs The installation of the FIK 5865 3 and FIK 5865 4 is identical The key switches and th...

Page 44: ... 4 36 After the FIK 5865 is con nected to the panel it must be added to the System This programming step is described in Section 4 12 Figure 4 36 FIK 5865 Connection to the FACP 4 11 2 FIK 5865 Mounting Mount the FIK 5865 4 to a standard 4 gang electrical box Mount the FIK 5865 3 to a standard 3 gang electrical box In Figure 4 37 the FIK 5865 4 attached to a 4 gang box is used as an example Figure...

Page 45: ...ription Labels 4 12 Configuring SBUS Modules This Section describes how to configure any System hardware modules that have been added to the System 4 12 1 Assigning SBUS Module IDs When you install a hardware module see Table 4 1 for compatible devices you must use the DIP switches on the module to assign an ID to the module The Address zero is an invalid address and is not allowed Figure 4 39 sho...

Page 46: ...s are available to customize the telephone lines These options are described in Section 9 6 Figure 4 40 Connection of Telephone Lines 4 14 Notification Appliance Auxiliary Power Circuits Four outputs are built in to the FCP 300 FACP which can be programmed to be used as the NACs Class A or Class B or pro grammed as the Aux power This Section of the manual explains how to install the conventional n...

Page 47: ...install a Class A notification appliance circuit do the following 1 Wire the Class A notification appliances as shown in Figure 4 42 Current Maximum Impedance 1 0A 3Ω 1 5A 2Ω 2 0A 1 5Ω 2 5A 1 2Ω 3 0A 1 0Ω Table 4 5 Maximum Impedance Class A Alarm Polarity 4 7 kΩ EOL Supervised Power Limited Notification Wiring Max Impedance All Circuits are Synchronized Regulated Rated at 27 4 VDC 3A Max CAUTION F...

Page 48: ...der circuits have a 24 volt power present at their terminals Any alarm will cause power to disconnect The power will be re applied when the System is reset If the AC power is off for more than 15 seconds the auxil iary door holder power will be disconnected to conserve the battery backup When the AC power is restored the power is immediately restored to the door holder circuits Constant Power Use ...

Page 49: ... or Relay 2 as needed for your application See Figure 4 43 for the location of the relay terminals 2 Configure the relay through programming see section 9 5 4 16 Remote Station Applications 4 16 1 Keltron Model 3158 Installation The control panel is compatible with the Keltron Model 3158 that is used for the direct connection to a Keltron receiver The 3158 reports alarms supervisories and troubles...

Page 50: ...arm Current 1 Amp for 1 second 27 2 VDC max The maximum coil and wire resistance combined must not exceed 30 ohms To install the 5220 for city box connection do the following 1 Use one of the knockouts on the right side of the control panel to connect the 5220 using a short piece of conduit must not exceed 20 feet in length 2 Wire the 5220 to the control panel as shown in Figure 4 45 This drawing ...

Page 51: ...ar the condition and reset the control panel Figure 4 45 City Box Connection 4 17 Using the Addressable Relay Module for City Box Connection Wire the Relay module as shown in Figure 4 46 Figure 4 46 Relay Module for City Box Connection Note NAC Circuit 2 Used as an example Any NAC circuit could be used Non Supervised Non Power Limited Intended for connection to a Note The shunt connection is recog...

Page 52: ...e NAC circuit used for this application 3 Connect earth ground wire to the 5220 chassis with mounting screw 4 Program the NAC circuit used as continuous and non silencing Refer to Section 9 5 for point programming Section 9 4 for group settings and Section 9 3 for zone settings and mapping It is not possible to reset the remote indication until you clear the condition and reset the control panel 5...

Page 53: ...shown in Figure 4 48 Do not install an EOL resistor on the terminals of the NAC circuit used 2 Program the NAC circuit as a notification circuit See Section 9 5 4 3 Map the group to activate the constant on from the zone event 4 Program the output group characteristics as non silenceable and reverse polarity Figure 4 48 Polarity Reversal Connection Using the 7644 L8 NOTE Use only NAC circuits on t...

Page 54: ...of a UL 864 Listed Remote Station Transmitter to the FCP 300 FACP dry contacts The FACP contacts must be supervised by the Remote Station Transmitter module using the end of line resistors ELRs with a value determined by the Transmitter Manufacturer Power is also provided by the Remote Station Transmitter Manufacturer Refer to the remote station Transmitter Manufacturer s Manual for details Figure...

Page 55: ...mited to 32 panels in the network with each site comprised of only one panel 5 1 2 Wiring Options Requirements to Connect Networked Panels 1 Fiber Optic Single Mode Use the FIK NIC and FIK FSL for up to 30dB loss of signal separation The FIK FSL connects to the network using 9 125 micron single mode fiber 2 Fiber Optic Multi Mode Use the FIK NIC and FIK FML for up to 8dB loss of signal separation ...

Page 56: ... network interface card with each panel The FIK NIC connects to other networked units using unshielded twisted pair wiring or fiber optic cable Figure 5 3 FIK NIC Network Interface Card 5 3 1 Fiber Loop Modules Two types of fiber optic modules are available to use to transmit and receive communication with the FIK NIC See Figure 5 4 Figure 5 4 Types Fiber Loop Modules FIK FSL Single Mode Fiber FIK...

Page 57: ...that allows the single mode fiber to network between nodes Each fiber loop module can Transmit TX and Receive RX the fiber optic cable connecting to the FIK NIC Up to two fiber loop cards can be added to the FIK NIC and both cards may be combined in the same configuration See Figure 5 5 Figure 5 5 FIK NIC with Fiber Loop Modules Accessory Mounting Kits The FIK NIC can be mounted within the FCP 300...

Page 58: ...h fault detection for any wiring at Port 2 of TB2 is done at the next previous FIK NIC due to these wiring connections being connected to Port 1 of TB2 at the next previous FIK NIC 4 Unused optic ports on fiber loop modules must have their dust caps placed on the port 5 Based on the type of data medium chosen run the twisted pair wiring fiber optic cable to the next FIK NIC using a Class B or Clas...

Page 59: ...59 Fiber Optic Multi Mode Wiring between the Multiple Panels The Fiber optic cable between multiple panels is shown in Figure 5 8 Class A is shown with a dotted line Figure 5 8 Fiber Optic Wiring Multi Mode Example Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring Class A wiring ...

Page 60: ...abling is shown with dotted line Figure 5 10 Twisted Pair and Fiber Optic Combination Wiring Example 5 4 Setting the Network ID for each Panel The Network ID for each panel is set using the DIP switch positions 1 through 5 See Figure 5 11 below for possible DIP switch settings Figure 5 11 Network ID Settings Class A wiring NOTE It is important that much thought is given when choosing the network I...

Page 61: ...ir status to a Member in this Menu The Panels showing OK are currently responding on the network The Panels not showing OK have either been removed or are not responding due to the networking prob lems See Section 6 1 for Network Diagnostics 1 Enter the Installer Code The panel will automatically access the Main Menu 2 Select 6 for the Network Programming 3 Press 1 to enter the Learn Network Menu ...

Page 62: ...5 Access Codes The Access Codes provide the user access to the control panel functions Each Access Code can be customized for each user This feature allows some users the ability to access the programming and other higher level panel functions while other users may only need to access the lower level functions such as preforming fire drills or acknowledging trouble conditions Profile 1 is the prof...

Page 63: ...ch panel on the FCP 300 ECS network specifies which Network Communicator is used for reporting The Network Com municator capability of the FCP 300 ECS System allows all panels to use the same communicator providing an economical solution to reduce the number of paths required for reporting purposes A Communicator is specified by the panel number The Network Communicators will be used to report the...

Page 64: ...port the primary and the backup receiver numbers and report by point or zone Also the account number and the daily test option are associated with the receivers The table can have up to 99 rows 1 From the Main Menu 2 Select 6 for Network Programming 3 Press 6 to enter the Communicator Options Menu 4 Select 4 for the Communicator Reporting Table 5 Press to add rows Press ENTER to edit data Figure 6...

Page 65: ...6 3 2 Edit Voice Commands When you select a Voice Output Group to be activated by a zone the cadence pattern choice does not apply For the Voice Out put Groups one of six System wide voice commands will activate instead of the cadence pattern 1 Enter the Installer Code The panel will automatically access the Main Menu 2 Select 6 for the Network Programming Menu 3 Select 7 for the Voice Options 4 C...

Page 66: ... network options out of sync Use this Menu to redistribute the changed options to the rest of the network The user will be required to choose from which panel to source the option Scroll down through the informational message and press ENTER to view the Select Source screen 1 Enter the Installer Code The panel will automatically access the Main Menu 2 Select 6 for the Network Programming Menu 3 Se...

Page 67: ...sts Fire Drill Menu Indicator Test Walk Test No Report Walk Test With Report Communicator Test Clear History Buffer Point Functions Disable Enable Buffer Point Status Set SLC Device Address SLC Single Device Locator Network Programming cont Access Codes Select Profile 01 20 Panel Functions SLC Multi Device Locator Profile 1 is the profile that dictates what functions the Firefighter Key has access...

Page 68: ...t Primary Account Secondary Receiver Secondary Account Test Secondary Account Voice Options Choose Site Edit Timers Control Lockout Immediate Ti mer Never See Section 6 3 1 Auto Reset ECS Event 1 8 Never Timer Event Disabled Auto Reset ECS MIC Triggered Event Edit Voice Commands Fire Alarm See Section 6 3 2 Fire System Aux 1 Fire System Aux 2 Fire Zone Aux 1 Fire Zone Aux 2 Fire Supervisory Fire P...

Page 69: ...to the SLC devices For additional information on the type of device you want to install refer to the Section that describes the type of device CAUTION DISCONNECT POWER TO AVOID THE RISK OF ELECTRICAL SHOCK AND DAMAGE TO THE UNIT POWER SHOULD BE OFF AT THE CONTROL PANEL WHILE INSTALLING OR SERVICING Part Numbers Model Name Description Install Sheet PN FIK 2351 Photoelectric smoke detector I56 6632 ...

Page 70: ... length of all taps and the main bus must not exceed 40 000 feet This requirement must be met in addition to the maximum distance requirements for the various wire gauges Wire Requirements Distance in Feet meters Wire Type RECOMMENDED Twisted unshielded pair 12 to 18 AWG 3 31mm2 to 0 82 mm2 50 ohms maximum per length of Style 6 7 50 ohms per branch maximum for Style 4 loop 12 500 ft 3 810 m 9 500 ...

Page 71: ...or a T tap 7 4 3 Wiring FIK 6815 in Style 6 7 Class A Configuration Figure 7 3 illustrates how to wire the SLC loop for the Class A installations Figure 7 3 Class A SLC Configuration NOTE 1 Style 6 does not use short circuit isolator devices NOTE 2 Style 7 requires an isolator module as the first device on the in and the out loop NOTE 3 No t taps allowed on class A SLC loops ...

Page 72: ...Addressing Using the Rotary Dials 7 6 Addressing SD Devices This Section describes how to address the detectors and the modules See Table 7 1 for a list of detectors that are easily addressed at the FACP The Installer Code is required to perform this task To address do the following 1 Connect a detector base temporarily to the programming terminals as shown in Figure 7 5 You can use the same base ...

Page 73: ...y acts as a bridge between a group of wireless fire devices and a SLC loop on the FIK 300 ECS It is powered by the SLC loops or by a regulated external 24 VDC UL listed power supply For updated details about wireless devices system setup and operation see the SWIFT Smart Wireless Integrated Fire Technology Instruction Manual P N LS10036 001FK E NOTE The WIDP WGI or SK WGI as part of the wireless n...

Page 74: ...igns the correct detector type heat ionization or photoelectric so the Installer does not need to edit the device type for the detectors Any contact monitor modules on the System will be assigned type Manual Pull The Installer will need to manually change the switch type if the manual pull is not correct The first JumpStart Auto Programming creates one zone Zone 1 and assigns all input points to Z...

Page 75: ...3 Accept Configuration 1 If you are ready to make the JumpStart configuration permanent select 3 2 The System will prompt you if the installation contains any addressable duct detectors used If there are no duct detectors select 2 for No and skip to Step 8 If the System contains duct detectors select 1 for Yes and continue with Step 3 3 From the list that displays select the SLC that contains the ...

Page 76: ...76 FCP 300 FCP 300ECS Manual P N LS10145 002FK E A 3 12 2021 Programming Overview Mapping Overview Figure 8 2 Input Point Assignment Example ...

Page 77: ...d 40 types of Site events that can be mapped For each event type you can activate the output groups with specific output patterns Mapping examples are shown in Figure 8 4 Figure 8 5 Figure 8 7 System Zone Panel Site Fire Manual Pull Alarm System Aux 1 Alarm Fire Drill Water Flow Alarm System Aux 2 Alarm General Fire Alarm Detector Alarm heat or smoke detectors General Fire Supervisory Zone Aux 1 A...

Page 78: ...tatus Point Active SBUS Class A Trouble Site Silenced SLC Loop Trouble Voice Aux In 1 8 Alarm AC Loss Trouble F1 Key Active Battery Trouble F2 Key Active Ground Fault Trouble F3 Key Active Phone Line Trouble F4 Key Active Reporting Account Trouble Voice Aux in 1 2 Printer Trouble System Mic Active Aux Power Trouble Background Music System Switch Trouble Output Group Trouble System Zone Panel Site ...

Page 79: ...Mapping Overview Programming Overview FCP 300 FCP 300ECS Manual P N LS10145 002FK E A 3 12 2021 79 Figure 8 5 Example of Zone Events Mapped to the Output Groups and Patterns ...

Page 80: ...80 FCP 300 FCP 300ECS Manual P N LS10145 002FK E A 3 12 2021 Programming Overview Mapping Overview Figure 8 6 Example of Events Mapped to the Output Groups and Patterns within a Networked Site ...

Page 81: ...nts are mapped to the zones and the output groups Typically you would create the following two output groups for each zone The LED points are available when the Models FIK 5865 3 4 and or FIK 5880 are used with the System Figure 8 7 Example of LED Points Mapped to Output Groups applies to Models FIK 5865 3 4 and FIK 5880 one output group for alarms one output group for troubles ...

Page 82: ...rd annunciator or an FIK RA100 FIK RA1000 or FIK RA 2000 remote annunciator The following subsections describe the programming basics including a description of the editing keys available for program ming and how to navigate and move through the Programming Menus Section 9 contains the specific information about the individual programming options 8 4 1 Entering Exiting the Panel Programming To Ent...

Page 83: ...m a menu Enter the number of the option Enter numeric data Press the appropriate number on the annunciator Enter text alphanumeric data See Editing Text Using the Built In Programmer on page 206 for complete list of characters Select from a scrolling list Use up arrow and down arrow to move through a list of available options When the option you want to select is displayed press ENTER Table 8 3 Me...

Page 84: ...e Properties on page 122 Medium High Zone Accessory Opt Single Multi station Cadence 00 23 See Zone Accessory Options on page 124 CO Single Multi station Cadence 00 23 Local Zone Yes No View Zone Points Select Zone Section 9 4 2 Group Edit Group Select Group Group Name See Edit Group Name on page 124 Section Group Properties Voice Group Y or N Switch 1 64 Template Override Y or N Allow Sys Overrid...

Page 85: ...PUT LATCH NON LATCH ECS TAMPER LATCH NON LATCH ECS SUPER VISORY LATCH NON LATCH NOTIF1 2 3 4 5 6 OUTPUT PT Select Group AUX CONST AUX RESET AUX DOOR Point cont FIK Devices on Internal and External FIK 6815 Enter Pt Select Sensor4 5 RELAY1 2 3 4 5 6 OUTPUT PT Select Group Section 9 5 AUX RESET AUX DOOR SLC LED 1 6 LED Number 1 80 LED Function Notif Unused DETECTOR 2 3 4 5 2 WIRE SMOKE Select Zone W...

Page 86: ...Base 2 3 4 5 PHOTO DUCT1 2 3 4 5 6 No Accessory DCT RLY ION DUCT1 6 No Accessory DCT RLY 2 WIRE SMOKE 1 6 ACCLIMATE2 3 4 5 No Accessory SDR BAS RLY BAS I SdrBa Intelligent Sounder Base HEAT HT2 3 4 5 No Accessory SDR base RLY base I SdrBa Intelligent Sounder Base PHOTO HEAT2 3 4 5 No Accessory SDR BAS RLY BAS I SdrBa Intelligent Sounder Base BEAM2 3 4 5 SUP DET1 2 3 4 5 6 Same function as DETECTOR...

Page 87: ...e Latch or non latch Single station or Multi station Silence or Non Silence CO SUPR FIRE ALARM No Accessory SDR BAS Single station or Multi station Silence or Non Silence RLY BAS I SdrBA Intelligent Sounder Base Latch or non latch Single station or Multi station Silence or Non Silence CO SUPR FIRE SUPR No Accessory Single station or Multi station SDR BAS RLY BAS I SdrBA Intelligent Sounder Base La...

Page 88: ...tch and Non Latch feature only appear for WATERFLOW FIRE SUPERVISORY FIRE TAMPER ZONE AUX1 ZONE AUX2 System AUX1 System AUX2 ECS INPUT ECS TAMPER and ECS SUPERVISORY WATER FLOW FIRE SUPER VISORY FIRE TAMPER FIRE DRILL SILENCE RESET P A S ACK ZONE AUX 1 B SWITCH ZONE AUX2 Latch and Non Latch feature only appear for WATERFLOW FIRE SUPERVISORY FIRE TAMPER ZONE AUX1 ZONE AUX2 System AUX1 System AUX2 E...

Page 89: ...nction selected Edit Name Enter Name FIK 5880 FIK 5865 FIK Series Amplifiers Enter Point UNUSED Section 9 5 4 and Section 9 5 6 NOTIF Select Group Edit Name Enter Name FIK 5496 Edit Point UNUSED Section 9 5 5 B NOTIF Control Circuit Notif Output Select Group Super vised Yes or No A NOTIF AUX_PWR Constant Edit Name Aux Sync Aux Door Aux Reset FIK RVM FIK ECS FIK NVCM Enter Pt Select Function UNUSED...

Page 90: ...y DHCP Enable System Options cont Communication Options AlarmNet Timers Ethernet Supervise 75 sec 90 Sec 3 min 5 min 1 hr 24 hrs 30 days None 5 Minutes See AlarmNet Timers on page 138 Old Alarm Time 10 min 15 min 30 Minutes 1 hr 2 hrs 4 hrs 8 hrs 12 hrs 24hrs none 30 Minutes Phone Line Gains Dialing High High See Phone Line Gains on page 138 Low Normal Reporting Low Low Normal High Daytime Nightti...

Page 91: ...ay 9 AUX SYNC setting is only applicable for the B200S Sounder Base Daylight Saving Options Auto Daylight Saving Y Y Section 9 6 6 N DST Start Select week 1st 2nd 3rd 4th or Last Select month Section 9 6 6 DST End Edit Banner Refer to Editing Text Using the Built In Programmer on page 206 Section 9 6 7 System Options cont SLC Family FIK Section 9 6 8 SD SK Jump Start AutoPrg Y Yes N No See Section...

Page 92: ...SERS INSTALLERS AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product incorporates field programmable software In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 and UL 2572 certain programming features or options must be limited to specific values or not used at all as indicated below Programmi...

Page 93: ... module will not be added 9 2 3 Deleting a Module If you ever need to delete a module follow these steps You must be in the Main Menu to perform this task If necessary enter the Installer Code 1 Select 7 for the Program Menu 2 Press 1 to enter the Module Menu 3 Press 3 to delete a module 4 Select a module to delete 5 A Warning screen will display If you want to proceed with deleting the module sel...

Page 94: ...ll bring up a Smoke Sens Day and Night 2 separate widgets with sensitivity as being either low med high for each device Type of Delay Description 1 Count One Count No Delay When this option is enabled an alarm occurs immediately when a single device of any of the following types goes into alarm detector manual pull water flow Aux1 or Aux2 This operation is considered the most typical operation and...

Page 95: ...ite Operator to activate the Acknowledge switch If the Operator does not press the Acknowledge switch within 15 seconds the zone will go into alarm If the Operator presses the Acknowledge switch within 15 seconds a 180 second time frame will begin counting down This time frame allows the Operator to investigate the cause of the alarm If the Operator performs a reset within 180 seconds the alarm wi...

Page 96: ...tivation is used This option links the output group with a voice select switch on an FIK RVM or a switch expander for dynamic activation deactivation Template Override Is shown when it is set to Yes Dynamic Activation Is shown if a non voice group is assigned to a Select Dynamic Activation Switch Number Dynamic Activation Template Override Cadence This is shown when the Template override is set to...

Page 97: ...tional Timers Description Silence Inhibit Timed Silence after Inhibit If this option is selected the output group must be audible for a programmed number of minutes before it can be silenced If the condition that caused the output to activate has not cleared during the time frame the output can be silenced If you select this option select the timeframe in the delay field Range is 0 60 minutes Auto...

Page 98: ...w key Refer to Table 9 5 under the column heading Type Selection for a list of choices Type Selection Function Latching Option Comments UNUSED Select for SLC points that are unused DETECTOR PHOTO Spot photoelectric detectors ION Spot ionization detector HEAT Spot heat detector PHOTO DUCT Duct photoelectric detector ACCLIMATE Acclimate photoelectric detector HEAT HT High temperature heat detector P...

Page 99: ...on available from the annunciator When the switch is activated a fire drill begins when the switch is de activated the fire drill ends SILENCE This System level switch is an alternative way to silence the fire System It has the same effect as pressing the Silence key RESET This System level switch is an alternative way to reset the fire System It has the same effect as pressing the Reset key P A S...

Page 100: ...SWITCH CO Detector Switch CO SUPERVISORY DETECT SWITCH Latching CO Supervisory Detector Switch Non Latching NOTIF OUTPUT PT Select Group Output point a general use notification type Use for driving standard notification appliances AUX CONST Use constant power for applications that require a constant auxiliary power source Power is always present at constant circuits AUX RESET Use for auxiliary pow...

Page 101: ... System AUX1 System AUX2 ECS INPUT ECS TAMPER and ECS SUPERVISORY WATERFLOW FIRE SUPERVISORY FIRE TAMPER FIRE DRILL SILENCE RESET P A S ACK ZONE AUX1 ZONE AUX2 System AUX1 System AUX2 MANUAL RELEASE INTERLOCK STATUS POINT ECS INPUT User also has ECS Event Number 1 8 option for ECS INPUT Only available when an FIK NVCM is installed in the System ECS TAMPER ECS SUPERVISORY A SWITCH Same as B SWITCH ...

Page 102: ...w key to select the desired group zone then press ENTER 15 Edit point name Or press the right arrow key to skip module name edit 16 Repeat steps 10 through 15 for all input points 9 5 4 Point Programming for FIK 5496 To program module points 1 Enter the Installer Code The panel will automatically access the Main Menu 2 Select 7 for Panel Programming 3 Press 4 to enter Point Menu 4 Press the up or ...

Page 103: ... Press the up or down arrows to select the desired module Refer to Section Programming Menu Quick Reference on page 108 for available choices Press ENTER Figure 9 8 Programming Points Screen for the FIK NVCM or FIK RVM Modules 5 Enter the point number Press ENTER 6 Press the up or down arrows to select the type Switch or unused Press ENTER 7 Press the up or down arrows to select the function Press...

Page 104: ...ASE INTERLOCK STATUS POINT FIK 5880 input 41 48 SWITCH ECS INPUT The User also has the ECS Event Number 1 8 option for the ECS INPUT ECS TAMPER and ECS SUPERVISORY functions in both FIK 5880 and FIK NVCM FIK RVM choices Only available when an FIK NVCM is installed in the System to the FIK NVCM FIK RVM choice part ECS TAMPER ECS SUPERVISORY FIK 5496 UNUSED B NOTIF NOTIF OUTPUT supervised not superv...

Page 105: ...re 24hrs 12hrs 6hrs and 4 hrs NOTE The AM and PM are only available if the panel Clock Options are set for AMPM mode Otherwise the clock is in military time and AMPM is not selectable Phone Lines To access the phone lines screen do the following 1 Enter the Installer Code 2 Select 7 for the Program Menu 3 From the Program Menu select 5 for the System Options 4 Select 1 for the Communication Opts 5...

Page 106: ...Telephone System The selection made here must match the programming for this option in the Communication Configuration dialog box of HFSS 8 Enter the desired number of answer rings then press ENTER Dial Option TouchTone or Pulse 9 Press the up or down arrow to select the dial option then press ENTER Dial Format 10 Press the up or down arrow to select the pulse ratio for the Rotary Dialing option t...

Page 107: ...NTER Phone Line Unused This option is used so that you can set the unused phones lines to Yes so no auto test will be sent through that line This option is factory programmed as No 14 Select Y or N by pressing the up or down arrow key then press ENTER Edit Ethernet 1 Enter the Installer Code The panel will automatically access the Main Menu 2 Select 7 for Panel Programming 3 Select 5 for System Op...

Page 108: ...g Day Night Sensitivity Time and Days 9 6 3 Holiday Days Up to 18 dates can be designated as holidays When Day Night Sensitivity is enabled all photoelectric smoke detectors in the System will use night sensitivity for the entire day on days designated as holidays see Section Daytime Nighttime Sensitiv ity on page 108 To add or change a holiday follow these steps 1 Enter the Installer Code 2 Selec...

Page 109: ...from step 7 of Section Alarm Verify on page 109 8 Enter the number of hours 0 30 before a low AC report will be sent to the Central Station then press ENTER Change AC Line Frequency The panel s AC line frequency is selectable for 50 60 Hz or Internal AC Frequency feature dictates how the control panel will calculate time based on the AC line frequency used in the installation site The Internal opt...

Page 110: ... you must enable set to Yes the Automatic Daylight Savings Adjustment option under Daylight Savings Options The default val ues for the DST Start and End are DST Start The second Sunday in March DST End The first Sunday in November To set the start and end for Daylight Saving Time do the following 1 Press the up or down arrow to select the week 1st 2nd etc Daylight Saving Time starts Then press EN...

Page 111: ... NO from the Warning screen Then press ENTER 9 9 Voice Options Use the Programming Menu to modify the messages programmed into the FIK NVCM You can also modify other voice set tings 9 9 1 FIK NVCM Maintenance The FIK NVCM Maintenance Menu is used to program the custom messages into the FIK NVCM The messages can be recorded locally using the microphone 1 Select 7 for th Panel Programming 2 Select 8...

Page 112: ...mbly Figure 10 1 Control Panel Annunciator 10 2 1 LCD Display The Control Panel LCD displays the following These messages can be entered up to 160 characters displaying over four lines of 40 characters each When you press the Annunciator keys the Annunciator keys beep 10 2 2 Banner The Banner is the message that displays on the control panel when the System is in the normal mode no alarm or troubl...

Page 113: ...are correct press ENTER 10 4 2 Disable Enable a Point 1 Select 2 for the Point Functions 2 Select 1 for the Disable Enable Point Text of Custom Banner Text of Internal Banner Main Menu Options Description 1 System Tests Access to the Fire Drill Indicator Test Walk Tests Communicator Test Clear History Buffer Manual AlarmNet Registration and Manual Communicator Reset 2 Point Functions Enable Disabl...

Page 114: ...e new events as they occur In Networked setups each panel stores up to 1000 of its own events When you view the Event History in the panel the most recent 500 events from every panel in the site will be displayed When you use the HFSS Programming Tool all 1000 events from every panel in the network will be uploaded On the multi site displays pressing ENTER or the right arrow key brings you directl...

Page 115: ...requires that at least one daily test in the network be enabled in Communicator Programming 3 The Manual Communicator Test will be communicated out both Phone Lines and Ethernet paths if they are all programmed Each Manual Communicator Test will alternate between one of the Phone Line paths and one of the AlarmNet paths 10 4 8 Manual AlarmNet Registration 1 From the Main Menu press 1 for System Te...

Page 116: ...oint Status 3 Select the module where the point you want to check is located 4 Enter the number of the point you want to check and press ENTER 5 A screen similar to those shown in Figure 10 3 will display Figure 10 3 Checking Detector Sensitivity Compliance You can print the detector status by uploading the detector status to the HFSS Programming Tool Then from the HFSS you can print the detector ...

Page 117: ...riority event active on each Sys tem When both Systems are active the System with control will activate System Override The System Override is activated on the lower priority non System Control Panel System Fire or Emergency System 10 5 2 System Override The System Override temporarily disengages the output group activations from the System being overridden This is done to prevent conflicting mess...

Page 118: ...priority is considered here based on the Event Priority Table If an output group is mapped both directly and through an output group template to an event the direct map gets priority Example Template 1 Contains Group 1 Zone 1 Manual Pull is mapped to Template 1 and Group 1 using constant and ANSI patterns respectively If Zone 1 Manual Pull is active Group 1 will output ANSI When an event is mapped...

Page 119: ...de to activate the User or Installer Menu Alarm A smoke detector goes into alarm or a pull station is activated The System will report events to the Central Station The on board annunciator will sound loud steady beeps to distinguish Alarm signals For Fire Alarm the sequence is a loud steady beep Any notification devices attached to the System will also sound For ECS Alarm the sequence is four sec...

Page 120: ...ble A screen similar to this one displays Press SILENCE to silence the annunciator Once the trouble condition has been fixed the System will restore itself automatically Prealarm A single detector trips in a 2 Count zone 2 Count means two detectors must trip before an alarm is reported Touchpad PZT beeps The LCD displays a screen similar to this one Press down arrow to view the Prealarm A screen s...

Page 121: ...ouble Interlock Zone operation requires an interlock switch input in the System and the Single Interlock Zone does not An interlock switch is typically a dry contact pressure switch When the Single or the Double Interlock Zone releasing is selected using HFSS Programming Tool the software suite will automatically default the following System parameters Output Group 2 is created Output Group 2 will...

Page 122: ... DC Rated Current Milliamp Asco T8210A107 24 VDC 700 8210G207 24 VDC 442 HV2740607 24 VDC 375 HV2838521 24 VDC 375 HV2740608 24 VDC 375 Honeywell Skinner 701X7028 24 VDC 917 Barnbrook System EA45 24 VDC 200 Kidde Fenwal 890181 24 VDC 2000 486500 24 VDC 290 895630 24 VDC 2000 897494 24 VDC 1500 Minimax 88 7363 24 VDC 1040 88 5738 24 VDC 1040 88 9323 24 VDC 500 Nohmi Bosai R85M10 24 VDC 1200 Parker ...

Page 123: ...put Activation If two addressable detectors a manual release switch is activated or an interlock switch is active the Interlock Release Alert and Detector Alarm outputs will activate Conditions Required for a Interlock Release Alarm Output Activation Any release requires the activation of an interlock switch and either a manual release switch or 2 activated addressable detec tors When these condit...

Page 124: ...al points 4 Once you are finished with disabling or activating points output groups enter the F Key Recording Menu again and select the End FKEY Recording option 5 The panel will return to the Idle screen 10 9 2 Aborting an F Key Macro Recording Session 1 After an F Key macro recording session has been started the session can be canceled at any time by accessing the F Key Recording Menu and select...

Page 125: ...expander modules ECS Control Key Pressing the ECS Control Key will do one of two things 1 Enter the Message Mode of the LOC ECS interface including trying to gain ECS Control if the user doesn t have it already 2 Relinquish the ECS Control if pressed while in the Message Mode ECS Control LED The ECS Control LED is used to indicate the status of the ECS Control in the System When the LED is on soli...

Page 126: ...ters an access code with the ECS Super User profile option The LOC lockout timer can be set between immediate and 12 hours in increments of 1 second or it can be set to never expire The default setting is 30 seconds The LOC lockout timer is restarted upon any key press at the LOC with ECS control The LOC lockout timer is cleared when ECS Control is relinquished User Profile Access Control The user...

Page 127: ...n to take place in The Select Key red LED will become lit and the circuits in the output group s will become active and play the currently active ECS event message when activated When deactivated the Select Key red LED will become unlit and the circuits in the output group s will become inactive Non voice output groups can also be assigned to Select Keys and will toggle on off using the activation...

Page 128: ...ty and LOC lockout timer are ignored when passing ECS Control between ECS Super Users at LOCs If another ECS Super User attempts to gain ECS Control from an LOC an ECS Control request is presented to the ECS Super User at the LOC that currently has ECS Control 11 4 ECS Point Functionality Any input point in the System can be configured as an ECS input The Point ECS 1 8 Alarm input types can be use...

Page 129: ...e following 1 Enter the Installer Code The panel will automatically access the Main Menu 2 Select 7 for the Program Menu 3 Press 1 to enter the Module Menu 4 Press 1 to edit a module 5 Use the up or down arrow key to select the module you want to edit 6 Press the right arrow key or press ENTER to move the cursor to the next selection 11 6 LOC Programming The Device Priority is a programmable optio...

Page 130: ...nt This event is activated by gaining ECS Control at an LOC and using the microphone without any ECS event already active in the Manual ECS State In this case the Mic Triggered ECS Alarm mapping and the General ECS Alarm mapping will be acti vated and stay activated until a different ECS event is activated at the LOC or the user resets the Emergency Communication System 11 7 3 Fire Page A Fire Pag...

Page 131: ...Record Mode select Keys 1 15 to use to reference Message Slots 1 15 The associated green Select Key will indicate that a message is currently programmed in the corresponding slot When there is no message recorded or the message is erased the associated green Select Key LED will be off While recording a particular message the red Select Key will turn on until the recording is completed The Select K...

Page 132: ...sage Key 3 and start playing the audio source on the PC or laptop 10 When the audio file from the PC is finished playing press ECS Message Key 3 again to stop the recording The Select Key green LED will come on 11 To playback the recorded message press the Select Key 1 15 that was just recorded to Recording with Aux Audio Input Example The user wants to record into memory slot 2 via the Aux Audio ...

Page 133: ... speak your message 8 Release the PTT button on the microphone to save your message The Select Key green LED for this location will turn on 9 To playback the recorded message press the Select Key 1 15 that was just recorded to 10 If you are not satisfied with the recorded message erase it see Section 11 8 3 and then repeat steps 1 through 7 Recording with Microphone Example User wants to record a ...

Page 134: ... A user would generally pick the audio circuit that is in closest proximity to them 6 Press ECS Message Key 8 on the FIK NVCM press the Select Key 1 15 that you wish to erase The Select Key red LED will stay on until the erase is done When erased the Select Key green LED by corresponding to the message slot you erased will go off 11 8 4 Using HFSS Voice Message Load Software The HFSS Voice Message...

Page 135: ...be selected as a destination panel for the network paging Network paging functions as an all call on the destination panel s all speaker circuits will be activated with the network paging audio on a destination panel the following need to be considered Priority 1 Local microphone is higher priority than network paging a user can page from their local panel even if the local panel is currently rece...

Page 136: ...er 001 Auto dialer test communications trouble line 1 restore YK 1 YKNN000001 3 350 Receiver 001 Auto dialer test communications trouble line 2 YC 2 YCNN000002 1 350 Receiver 002 Auto dialer test communications trouble line 2 restore YK 2 YKNN000002 3 350 Receiver 002 Automatic test normal RP 0 RPNN000000 1 602 00 000 Automatic test off normal RY 0 RYNN000000 1 608 00 000 Battery voltage trouble Y...

Page 137: ... Repeater ground fault trouble EM 0103 EMNN000103 1 334 Panel ID 103 Repeater ground fault trouble restore EN 0103 ENNN000103 3 334 Panel ID 103 Repeater missing trouble EM 0100 EMNN000100 1 334 Panel ID 100 Repeater missing trouble restore EN 0100 ENNN000100 3 334 Panel ID 100 Repeater Rx1 communication trouble EM 0101 EMNN000101 1 334 Panel ID 101 Repeater Rx1 communication trouble re store EN 0...

Page 138: ... switch trouble UT 0000 UTNN000000 1 373 00 000 External Reset Silence Fire Drill switch trouble restore UJ 0000 UJNN000000 3 373 00 000 LOC Mic Activated ECS Alarm QA 0 QANN000000 1 220 00 000 LOC Mic Activated ECS Alarm Restore QH 0 QHNN000000 3 220 00 000 LOC Point ECS Alarm QA Emergency QANN0E0000 1 220 Emer gency 00 000 LOC Point ECS Alarm Restore QH Emergency QHNN0E0000 3 220 Emer gency 00 0...

Page 139: ...store SJ Zone SJNN000ZZZ 3 373 00 Zone Zone based AUX1 switch alarm UA Zone 1000 UANN001ZZZ 1 140 01 Zone Zone based AUX1 switch alarm restore UH Zone 1000 UHNN001ZZZ 3 140 01 Zone Zone based AUX1 switch trouble UT Zone 1000 UTNN001ZZZ 1 373 01 Zone Zone based AUX1 switch trouble restore UJ Zone 1000 UJNN001ZZZ 3 373 01 Zone Zone based AUX2 switch alarm UA Zone 2000 UANN002ZZZ 1 140 02 Zone Zone b...

Page 140: ... Exp ID Point ECS Supervisory Tamper Alarm pi Exp ID QS Point QSNNXXPPPP 1 241 Exp ID Point ECS Supervisory Tamper Alarm Restore pi Exp ID QR Point QRNNXXPPPP 3 241 Exp ID Point ECS Supervisory Tamper Trouble pi Exp ID QT Point QTNNXXPPPP 1 242 Exp ID Point ECS Supervisory Tamper Trouble Restore pi Exp ID QJ Point QJNNXXPPPP 3 242 Exp ID Point ECS Supervisory Tamper Disabled pi Exp ID QB Point QBN...

Page 141: ...led pi Exp ID FU Point FUNNXXPPPP 3 571 Exp ID Point Manual release switch trouble Water Release Zone pi Exp ID FT Point FTNNXXPPPP 1 373 Exp ID Point Manual release switch trouble restore Water Release Zone pi Exp ID FJ Point FJNNXXPPPP 3 373 Exp ID Point Notification output point disabled pi Exp ID FB Point FBNNXXPPPP 1 571 Exp ID Point Notification output point enabled pi Exp ID FU Point FUNNXX...

Page 142: ...PP Point UANNXX6PPP 1 174 Exp ID Point Voice Aux ECS 4 Point Alarm Restore pi Exp ID UH 6PPP PPP Point UHNNXX6PPP 3 174 Exp ID Point Voice Aux ECS Point Trouble pi Exp ID UT Point UTNNXXPPPP 1 379 Exp ID Point Voice Aux ECS Point Trouble Restore pi Exp ID UJ Point UJNNXXPPPP 3 379 Exp ID Point Voice Aux ECS Point Disabled pi Exp ID UB Point UBNNXXPPPP 1 580 Exp ID Point Voice Aux ECS Point Enabled...

Page 143: ...Exp ID Point Zone based AUX2 switch trouble restore pi Exp ID UJ Point UJNNXXPPPP 3 373 Exp ID Point System based Wireless Gateway Trouble pi Exp ID UT Point UTNNXXPPPP 1 373 Exp ID Point System based Wireless Gateway Trouble restore pi Exp ID UJ Point UJNNXXPPPP 3 373 Exp ID Point Wireless Gateway Trouble pi Exp ID UT Point UTNNXXPPPP 1 373 Exp ID Point Wireless Gateway Trouble restore pi Exp ID ...

Page 144: ...e For examples see Table 12 4 Fire Trouble Nac Zone n a 98 n a Nac Circuit 7 EE ZZZ FT400 ZZZ OPG Event Report Zone Point Panel ID Module Zone ZZZZ Point ZZZZ Fields Sent SIA Event Data Table 12 3 SIA Panels PI Modifier Reporting Examples Event Report Zone Point Panel ID PP Module MM Zone ZZZZ Point ZZZZ Fields Sent SIA Event Data Fire Alarm Zone Zone 32 n a 15 n a EE PP MM ZZZZ FA32000015 Fire Al...

Page 145: ...in the required range To measure impedance use the following procedure 1 Disconnect both wires from the terminal block at the panel SLC devices can remain connected 2 Measure the impedance from positive to negative and from negative to positive Both measurements should be greater than 500 K ohms If the installation uses T taps test each T tap individually 3 Temporarily connect the positive wire to...

Page 146: ... the left arrow you will exit back to the Point Function Menu If you select ENTER the System will cease normal operation leaving the premise unprotected 4 Select the SLC loop 5 Enter the SLC address of the device you want to locate The LED on the selected device will start flashing 6 To exit the SLC Device Locator press the left arrow key 13 3 2 SLC Multiple Device Locator This feature operates in...

Page 147: ... is on 4 Make any selections specific to the module selected in the previous step 5 Use the up or down arrow key to select the point you want to test 6 Press ENTER to toggle Active Inactive Output 7 Press the left arrow key to exit 13 3 4 Earth Fault Resistance Table 13 2 lists the Earth Fault Resistance Detection for each applicable terminal on the FACP NOTE Once you exit the System will resume n...

Page 148: ...d 43 On board 15 On board 44 On board 16 On board 45 On board 17 On board 46 On board 18 On board 47 On board 19 On board 48 On board 20 On board 49 On board 21 On board 50 On board 22 On board 51 On board 23 On board 52 On board 24 On board 53 On board 25 On board 54 On board 26 On board 55 On board 27 On board 56 On board 28 On board 57 On board 29 On board 58 On board 59 On board 103 On board 6...

Page 149: ...rd 136 On board 93 On board 137 On board 94 On board 138 On board 95 On board 139 On board 96 On board 140 On board 97 On board 141 On board 98 On board 142 On board 99 On board 143 On board 100 On board 144 On board 101 On board 145 On board 102 On board 146 On board 147 On board 154 On board 148 On board 155 On board 149 On board 156 On board 150 On board 157 On board 151 On board 158 On board 1...

Page 150: ...oint Record This chart can be used to keep track of how conventional output points circuits have been configured Module Addr Zone Group Description Module Addr Zone Group Description Table 14 2 Installation Record of Devices Installed on SLC Continued Point Circuit Group Description 1 2 3 4 5 6 7 8 Table 14 3 Conventional Output Point Record ...

Page 151: ... work with this feature This control is UL listed for panel wide Synchronization Manufacturer Model Audio Visual Type AMSECO SH24W 153075 x x Horn Strobe SAD24 153075 x Strobe SAD24 75110 x Strobe SL24W 75110 x Strobe SL24C 3075110 x Strobe SLB24 75 x Strobe RSD24 153075 x Strobe RSD24 75110 x Strobe SH24W 75110 x x Horn Strobe SH24W 3075110 x x Horn Strobe SHB24 75 x x Horn Strobe SCM24W 153075 x...

Page 152: ... Horn Strobe P2430 FC x x Horn Strobe P2430W FC x x Horn Strobe P2430K FC x x Horn Strobe P2475 FC x x Horn Strobe P2475W FC x x Horn Strobe P2475K FC x x Horn Strobe P24110 FC x x Horn Strobe P24110W FC x x Horn Strobe P24110K FC x x Horn Strobe S2430W FC x Strobe S2430K FC x Strobe S2475 FC x Strobe S2475W FC x Strobe S2475K FC x Strobe S24110 FC x Strobe S24110W FC x Strobe S24110K FC x Strobe ...

Page 153: ... x x Multi Candella Horn Strobe Ceiling Mount GCCR24 x Multi Candella Horn Strobe Ceiling Mount GCS24 x Multi Candella Strobe Ceiling Mount GCSR24 x Multi Candella Strobe Ceiling Mount GECR 24 x x Multi Candella Horn Strobe GES24 15 x Strobe GES24 30 x Strobe GES24 60 x Strobe GES24 75 x Strobe GES24 110 x Strobe GES24 15 75 x Strobe GES24 177 x Strobe GES3 24 x Multi Candella Strobe GESR 24 x Mul...

Page 154: ... PC2R P x x 2 Wire Horn Strobe P2RH x x 2 Wire Horn Strobe High Candela P2RH P x x 2 Wire Horn Strobe High Candela PC2RH x x 2 Wire Horn Strobe High Candela PC2RH P x x 2 Wire Horn Strobe High Candela P2W x x 2 Wire Horn Strobe P2W P x x 2 Wire Horn Strobe PC2W x x 2 Wire Horn Strobe PC2W P x x 2 Wire Horn Strobe P2WH x x 2 Wire Horn Strobe High Candela P2WH P x x 2 Wire Horn Strobe High Candela P...

Page 155: ... Wall 4X4 PC4RL x x Horn Strobe 4W Red Ceil 4X4 PC4WL x x Horn Strobe 4W WHT Ceil 4X4 SR x Strobe SR P x Strobe SCR x Strobe SCR P x Strobe SRH x Strobe High Candela SRH P x Strobe High Candela SCRH x Strobe High Candela SCRH P x Strobe High Candela SW x Strobe SW P x Strobe SCW x Strobe SCW P x Strobe SWH x Strobe High Candela SWH P x Strobe High Candela SCWH x Strobe High Candela SCWH P x Strobe...

Page 156: ...Horn Weatherproof AH 24WP x Horn Weatherproof AMT 241575W x x Multi Tone Horn Strobe AMT 24MCW x Mutli Tone Horn Strobe AMT 241575W NYC x x Multi Tone Horn Strobe AMT 12 24 x Multi tone Horn AMT 12 24 NYC x Multi tone Horn AS 121575W x Horn Strobe NH 12 24 x x Horn AS 241575W x x Horn Strobe AS 24MCC x x Horn Strobe AS 24MCCH x x Horn Strobe AS 24MCW x x Horn Strobe AS 24MCWH x x Horn Strobe ASWP ...

Page 157: ... Horn Strobe MTWPB 2475W x x Multitone Horn Strobe MTWPG 2475W x x Multitone Horn Strobe MTWPR 2475W x x Multitone Horn Strobe MTWPA 24MCCH x x Multitone Horn Strobe ZNH x Horn NS 121575W x x Horn Strobe NS 241575W x x Horn Strobe NS 24MCW x x Horn Strobe NS 24MCC x x Horn Strobe NS 24MCCH x x Horn Strobe ZNS MCW x x Horn Strobe ZNS MCWH x x Horn Strobe ZNS 24MCC x x Horn Strobe ZNS 24MCCH x x Hor...

Page 158: ...oof RSSWP 24MCWH x Strobe Weatherproof ZRS MCWH x Strobe ZRS 24MCC x Strobe ZRS 24MCCH x Strobe MB G6 24 x Motor Bell MB G10 24 x Motor Bell MB G6 12 x Motor Bell MB G10 12 x Motor Bell MIZ 24 R x Mini Horn MT 12 24 R x x Multitone Horn MT4 12 2z x x Multitone Horn ZRS MCW x Strobe MTWPR 24MCCH x x Multitone Horn Strobe NH 12 24R x Horn HSR x Horn Strobe HSW x Horn Strobe STR x Strobe STW x Strobe...

Page 159: ... 16 loop 2451TH B401B A N A 16 loop 2W B A N A 20 loop 2WT B A N A 20 loop 2WTA B A N A 1 loop 2WTR B A N A 1 loop Table A 1 Compatible Two Wire Smoke Detectors Style B Smoke Detector Base Detector Type Max Standby Current mA Alarm Current mA Fenwal CPD 7021 w 70 201000 005 Base Ionization 0 10 Fenwal PSD 7125 Photoelectric 0 10 Fenwal PSD 7126 w 70 201000 005 Base Photoelectric 0 10 Fire Lite BLP...

Page 160: ...otoelectric 0 10 41 System Sensor 2451 Photoelectric 0 10 39 System Sensor 2451TH with B402B Base Photoelectric 0 10 39 System Sensor 2W MOD Loop Test Maintenance Mod 30 50 System Sensor 4W B 12 24 Volt Photoelectric I3 05 23 System Sensor4WT B 12 24 Volt Photoelectric I3 w Therm 05 23 System Sensor 4WTA B 12 24 Volt I3 Photo w Therm Sounder 05 35 System Sensor 4WTR B 12 24 Volt I3 Photo w Therm R...

Page 161: ... mA Edwards DH150A Floor Mount 96 Edwards DH154A Flush Mount 96 Edwards DH158A Surface Mount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon Firemark FM 998 Concealed Wiring 68 Table A 3 Compatible Door Holders Manufacturer Model Current mA Air Products Controls LTD MR 101 C MR 201 C PAM 1 PAM 2 PAM SD 15 35 15 15 15 System Sensor A77 716B PR 1 PR 2 PR ...

Page 162: ... Amber Lens ALERT White SPSW CLR ALERT Wall High Fidelity Speaker Strobe Clear Lens ALERT White SPSW P Wall High Fidelity Speaker Strobe Plain Red SPSWH Wall High Fidelity Speaker Strobe High Candela White SPSWH P Wall High Fidelity Speaker Strobe High Candela Plain Red SPRL Wall High Fidelity Speaker Red SPWL Wall High Fidelity Speaker White SPCRL Ceiling High Fidelity Speaker Red SPCWL Ceiling H...

Page 163: ...s enter to accept B 2 Example Name Edit 1 Press the up or down arrow to select the upper case letters mode Press 2 until the F appears 2 Press the up or down arrow to change mode to lower case letters Press 3 until the i appears 3 Press 6 until the r appears 4 Press 2 until the e appears 5 Press 0 to add a space then continue to the next word using the same process 6 Press ENTER to accept Figure B...

Page 164: ... Numbers 1 1 2 3 4 2 5 6 7 8 3 9 10 11 12 4 13 14 15 16 5 17 18 19 20 6 21 22 23 24 7 25 26 27 28 8 29 30 31 32 9 33 34 35 36 10 37 38 39 40 11 41 42 43 44 12 45 46 47 48 13 49 50 51 52 14 53 54 55 56 15 57 58 59 60 16 61 62 63 64 17 65 66 67 68 18 69 70 71 72 19 73 74 75 76 20 77 78 79 80 21 81 82 83 84 22 85 86 87 88 23 89 90 91 92 24 93 94 95 96 25 97 98 99 100 26 101 102 103 104 27 105 106 107...

Page 165: ...al P N LS10145 002FK E A 3 12 2021 165 Appendix D Cadence Patterns Figure D 1 The cadence patterns shown in Appendix D are available for use with the control panel Figure D 2 Cadence Patterns Available with the Control Panel ...

Page 166: ... to a unique password Securely configure networks and firewalls Assess security risks Develop a Disaster and Recovery Plan Develop a Backup and Recovery Strategy Install configure and keep anti virus software updated on all computers which access the panel Keep operating system updated on all computers which access the panel Deliver all required system information upon delivery to the system owner...

Page 167: ...FIKE CORPORATION 704 SW 10th Street Blue Springs MO 64015 Telephone 1 816 229 3405 www fike com ...

Page 168: ...nt Status 3 From the list that displays select the SLC module where the point you want to view is located 4 The fourth line of the display shows the Sensitivity Status NORMAL means the detector is in compliance with NFPA 72 CAL MAINT means the detector is in compliance with NFPA 72 but maintenance should be performed soon CAL TRBLE means the detector is not in compliance with NFPA 72 Set Time and ...

Page 169: ...Cut Along the Dotted Line ...

Page 170: ...prompted OR 1 Enter the Installer Code The panel will automatically go to the Main Menu 2 Press 1 to select System Tests 3 Enter code if prompted then press 1 to select Fire Drill 4 Press ENTER to start the fire drill and Press ENTER to end the fire drill Set Time and Date 1 Press ENTER to access the Main Menu 2 Then press 4 to select the Set Time Date Enter a code if prompted 3 Make changes in th...

Page 171: ...Cut Along the Dotted Line ...

Page 172: ...age ECS Control LED Green Blink When this LED is blinking someone has requested control of the ECS System On LOC has ECS Control and the user is able to make the changes to the ECS Off LOC does not have ECS Control ECS Message LED Red On The corresponding ECS event was activated by an ECS device Off The corresponding ECS event was not activated from this LOC Green On The corresponding ECS event is...

Page 173: ...Cut Along the Dotted Line ...

Page 174: ...nate If another LOC has ECS Control the display will be similar to the one shown Press 1 to request control The LOC with ECS Control will then be able to allow or deny the request Gain ECS Control as ECS Super User at an LOC only one ECS Super User is allowed ECS Control in the System at a time From the Idle screen enter an ECS Super User access code and then press the ECS Control Key If ECS Contr...

Page 175: ...Cut Along the Dotted Line ...

Reviews: