126
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
Emergency Communication System Operation
LOC Functionality
2.
Red LEDs: active areas for System events.
Figure 11.1 FIK-NVCM/ FIK-RVM Front View
11.2.2 Gaining ECS Control
When attempting to gain ECS Control, there are three things that govern whether or not ECS Control can be obtained:
1.
LOC Priority.
2.
LOC Lockout.
3.
User profile access control.
LOC Priority
LOCs are assigned (through panel or HFSS Programming Tool programming of the FIK-NVCM or FIK-RVM) an LOC prior-
ity of low, normal, or high. The LOCs with a higher priority are always able to gain control from a lower priority LOC.
LOC Lockout
When LOCs are programmed to the same priority, the setting LOC lockout applies. LOC lockout will not allow an LOC to
gain ECS Control from the LOC with ECS Control until one of three things happen:
1.
The LOC lockout timer expires. Once the LOC lockout timer expires, an attempt to gain ECS Control can be made again.
2.
The user at the second LOC requests ECS Control from the LOC with ECS Control and that LOC grants the request. (See
Section 11.2.7). If the ECS lockout timer expires while an ECS Control request is in progress, the System will
automatically pass ECS Control to the requesting LOC.
3.
The user at the second LOC enters an access code with the ECS Super User profile option.
The LOC lockout timer can be set between immediate and 12 hours in increments of 1 second or it can be set to never expire.
The default setting is 30 seconds. The LOC lockout timer is restarted upon any key press at the LOC with ECS control. The
LOC lockout timer is cleared when ECS Control is relinquished.
User Profile Access Control
The user will need to enter an access code containing the ECS Control Request or ECS Super User profile option to gain ECS
Control. ECS Control Request and ECS Super User profile options will be mutually exclusive to the System. If the access code
has ECS Super User, the ECS Control Request is ignored and activations by that user are always as ECS Super User.
11.2.3 Manual ECS
After gaining ECS Control the System enters the LOC ECS interface which allows you to activate the Emergency System and
allows for Emergency Paging. Once an emergency event has been activated the panel enters a Manual ECS State. In this state,
all ECS Alarm programmed points that are currently in alarm in the System are changed to an active state. The display status
screen reflects this when viewing the System for status. Any outputs that were activated by the ECS Alarm programmed points
ECS Control
Message
LEDs
Message
ECS Control LED
ECS CONTROL
Keys
Key
ALL CALL
Key
NON-ACTIVE CALL
Key
Select
Keys
READY
TO TALK
Select
LEDs
NOTE:
The lockout timer must be programmed to expire sometime other than Never.