Commissioning

Identification & Maintenance (I&M)
The “Identification & Maintenance” (I&M) function serves as an electronic rating plate of the interface
and offers uniform, manufacturer-independent access to device-specific online information over the
network.

PROFIenergy
The product supports the PROFIenergy profile for energy management. This makes it possible to
switch off specific consumers that are not required in order to reduce energy demand.

Crossover detection (auto MDI/MDI-X)
The product supports crossover detection (auto MDI/MDI-X), which means that there is the option of
using patch cables or crossover cables.

When using patch cables and crossover cables in the same network, crossover detection must be
activated in the higher-order controller.

Priority start-up (Fast Start-Up)
The "Fast Start-Up” function ensures that the automation system CPX-AP-A is able to start up quickly.

When using the “Fast Start-Up” function, crossover detection (auto MDI/MDI-X) must be deactivated.

5

Mounting

Carry out assembly according to the "Automation system CPX-AP-A operating instructions" 

è

 1.1

Applicable documents.

6

Installation

Carry out installation according to the "Automation system CPX-AP-A operating instructions"

è

 1.1 Applicable documents.

PROFINET Use network cables as described in the cable specification 

è

 10 Technical data.

7

Commissioning

NOTICE

Unauthorised Access to the Device Can Cause Damage or Malfunction.
• When connecting the device to a network, protect the network from unauthorised access.

Standards for security in information technology can be used for network protection measures, e.g.
IEC 62443, ISO/IEC 27001.

NOTICE

Malfunction due to switching on the higher-order controller and automation system CPX-AP in the
incorrect order.
• Switch on the higher-order controller and automation system CPX-AP according to the preset order

of the network used.

1. Set up an automation project for the higher-order controller using suitable software.
2. Load the device description file into the software.

Summary of Contents for PROFINET CPX-AP-A-PN-M12

Page 1: ...CPX AP A PN M12 PROFINET interface Operating instruc tions 8160756 2022 07 8160758...

Page 2: ...Translation of the original instructions PI PROFIBUS PROFINET is a registered trademark of its respective trademark holder in certain countries...

Page 3: ...qualified personnel 5 3 Additional information 5 4 Product overview 6 4 1 Structure 6 4 1 1 Product design 6 4 1 2 LED displays 6 4 1 3 Connecting elements 7 4 2 Function 7 5 Mounting 8 6 Installatio...

Page 4: ...om revision 1 Tab 2 Product version The product version can be determined from the product labelling There may be an updated version of this document for this or later product versions www festo com s...

Page 5: ...n a PROFINET IO net work Use the product only as follows Use only in an industrial environment Outside industrial environments e g in commercial and residential mixed use areas it may be necessary to...

Page 6: ...on for system communication XF20 3 LED display 4 PROFINET communication connection XF2 5 Inscription label optional 4 1 2 LED displays LED Meaning MD Module diagnostics green red PL Load supply green...

Page 7: ...controller and the modules of an automation system CPX AP A Data are transferred based on Industrial Ethernet following the IEEE 802 3 protocol Communication takes place in real time using the Real Ti...

Page 8: ...y When using the Fast Start Up function crossover detection auto MDI MDI X must be deactivated 5 Mounting Carry out assembly according to the Automation system CPX AP A operating instructions 1 1 Appl...

Page 9: ...lay components of the module after error free commissioning After error free commissioning the LEDs MD SD and PL are green The LEDs XF1 and XF2 light up green when there is a network connection Inform...

Page 10: ...gateway address 1 UINT32 ro 12007 MAC address 1 UINT8 ro 6 20000 Module code 1 UINT32 ro 20022 Configuration of voltage monitoring load supply PL 0 load voltage monitoring inactive 1 load voltage mon...

Page 11: ...it 6 is not valid for index 0 1 UINT8 ro Number of mod ules 1 1 ro read only rw read write Tab 7 AP parameter 9 Diagnostics and fault clearance 9 1 Diagnostics options Diagnostics via LED displays Sys...

Page 12: ...30 Load supply PL 24 V DC switched off Load supply PL 24 V DC switched off Remedy Check if emergency stop is active Check load supply Diag nostic status Information 02 01 013F 33620287 Overvoltage in...

Page 13: ...c status Warning 08 01 0124 134283556 AP master lost No communication with AP master possible Remedy Restart AP master Check communication cable AP Diag nostic status Error 08 01 0127 134283559 AP Mod...

Page 14: ...3578 Multiple AP Master detected Another AP Master with higher priority was recognized Remedy Check AP configuration Only one AP Bus Interface is allowed Restart AP System Diag nostic status Error 08...

Page 15: ...uring startup Automatic retry of startup triggered Remedy Check communication cable AP Check AP devices Check for firmware versions Diag nostic status Warning 08 01 01C4 134283716 AP Module s detected...

Page 16: ...iag nostic status Error 08 0A 017F 134873471 Process data mis match Reserved process length data for IO Link device too small Remedy Change module variant to a bigger process data length Diag nostic s...

Page 17: ...nostic image The version of the full diagnostic image is not supported Remedy Check firmware versions of master and devices and update to compatible versions Diag nostic status Error 0B 08 0190 185074...

Page 18: ...a sources of the device have inconsistencies regarding the same target data Remedy Possible Bug detected in the device Please contact Festo Service Diag nostic status Information Warning Error 0C 00 0...

Page 19: ...switching off load supply PL flashing red 0 5 Hz Module diagnostics active Degree of severity Warning e g parameterisation error Take appropriate remedial action e g check parameterisation red light M...

Page 20: ...stem diagnostics active Degree of severity Information e g load supply PL to a module not available or firmware update in a module active flashing red 0 5 Hz System diagnostics active Degree of severi...

Page 21: ...ble Check load supply PL flashing red 0 5 Hz Load supply PL outside the tolerance range Check load supply PL Tab 11 LED load supply PL Maintenance MT LED yellow Meaning Remedy off Maintenance not requ...

Page 22: ...t cor rect Check device name device number IO controller defective Fix IO controller Tab 13 LED PROFINET network fault NF PROFIenergy PE LED green Meaning Remedy off PROFIenergy not activated flashing...

Page 23: ...line mode of the control software and in the user program of the high order controller Diagnostic messages from the automation system CPX AP A that cannot be seen on the PROFINET standard diagnostics...

Page 24: ...ress space inputs outputs Byte Max 1024 1024 Number of AP stations Max 80 Module code hex dec 0x3081 12417d Module identification CPX AP A PN M12 Protection against electric shock protec tion against...

Page 25: ...s message over voltage in logic supply PS V DC 31 Electrical isolation supply Isolation present Mains buffering time logic supply PS ms 10 Load supply PL V DC 24 25 Intrinsic current consump tion at 2...

Page 26: ...8 Transmission rate Mbps 100 Crossover detection Auto MDI MDI X Cable length per segment m Max 100 Factory settings IP address 0 0 0 0 Subnet mask 0 0 0 0 Cable specification Cable type Ethernet twist...

Page 27: ......

Page 28: ...2022 all rights reserved to Festo SE Co KG Copyright Festo SE Co KG 73734 Esslingen Ruiter Stra e 82 Deutschland Phone 49 711 347 0 Internet www festo com...

Reviews: