12
Festo — CPX-AP-A-PN-M12 — 2022-07
Diagnostics and fault clearance
ID hex (dec)
Message
Description
02 | 01 | 0016
(33619990)
Undervoltage in logic
supply (PS) 24 V DC
Diag-
nostic
status
Error, Warning
02 | 01 | 0017
(33619991)
Overvoltage in logic
supply (PS) 24 V DC
Overvoltage in logic supply (PS) 24 V DC
Remedy
–
Check power supply.
Diag-
nostic
status
Warning
02 | 01 | 0105
(33620229)
Undervoltage in load
supply (PL) 24 V DC
Undervoltage in load supply (PL) 24 V DC
Remedy
–
Check power supply (load)
–
Check for short circuit.
Diag-
nostic
status
Error
02 | 01 | 0106
(33620230)
Load supply (PL) 24 V
DC switched off
Load supply (PL) 24 V DC switched off
Remedy
–
Check if emergency stop is active
–
Check load supply
Diag-
nostic
status
Information
02 | 01 | 013F
(33620287)
Overvoltage in load
supply (PL) 24 V DC
Overvoltage in load supply (PL) 24 V DC
Remedy
–
Check power supply.
Diag-
nostic
status
Error
06 | 00 | 0109
(100663561)
Startup parameter
rejected by device
The startup parameter specified in the AP device descrip-
tion does not exist in the device or is different from the
specification.
Remedy
–
Check firmware versions
Diag-
nostic
status
Error
06 | 00 | 010A
(100663562)
Mismatch in startup
parameter size
The length of the startup parameter in the device and the
AP device description do not match.
Remedy
–
Check firmware versions