26
Festo — CPX-AP-A-PN-M12 — 2022-07
Technical data
Network-specific data
Protocol
PROFINET
1)
With functionalities of Class C (CC-C)
–
LLDP
–
DCP
–
CiR
–
MRP, MRPD
–
FSU
–
IRT
–
S2 system redundancy
Specification
(Standards and norms with
reference to PROFINET)
IEC 61158, IEC 61784, IEC 61918
Transmission rate
[Mbps]
100
Crossover detection
Auto-MDI/MDI-X
Cable length per segment
[m]
Max. 100
Factory settings
IP address
0.0.0.0
Subnet mask
0.0.0.0
Cable specification
Cable type
Ethernet twisted pair cable, shielded
Transmission class
Category Cat 5 or higher
Cable diameter
[mm]
6 … 8
Wire cross section
[mm
2
]
0.14 … 0.75
AWG 22 (required for maximum connection length
between network stations)
1) based on the Ethernet protocol IEEE 802.3
Tab. 18: Network-specific data