16
Festo — CPX-AP-A-PN-M12 — 2022-07
Diagnostics and fault clearance
ID hex (dec)
Message
Description
08 | 01 | 0215
(134283797)
Device forced to com-
munication loopback
Diag-
nostic
status
Maintenance Required
08 | 01 | 0225
(134283813)
Invalid Topology
The current topology contains invalid connections.
Remedy
–
Check wiring
Diag-
nostic
status
Maintenance Required
08 | 01 | 880F
(134318095)
AP process data
internal error
The AP process data controller returns an error.
Remedy
–
Restart device
Diag-
nostic
status
Error
08 | 0A | 017F
(134873471)
Process data mis-
match
Reserved process length data for IO-Link device too small
Remedy
–
Change module variant to a bigger process
data length
Diag-
nostic
status
Error
0A | 00 | 01A7
(167772583)
Non-volatile memory
defect
Non-volatile memory defect
Remedy
–
Restart device
–
Contact Festo Service if problem persists
Diag-
nostic
status
Error
0B | 00 | 010E
(184549646)
General software
failure
An error occurred that could not be matched with any
other diagnosis.
Remedy
–
Check if you are using the latest firmware
revision
–
Contact the Festo Support
Diag-
nostic
status
Error
0B | 00 | 0140
(184549696)
Systemstart
The system is starting.
Remedy
–
None