Festo — CPX-AP-A-PN-M12 — 2022-07
Diagnostics and fault clearance
23
9.4
Diagnostics via Web Server
A webserver is available to display the diagnostics messages.
The web server can be accessed by entering the IP address in the address bar of a web browser.
9.5
Diagnostics via PROFINET IO
The automation system CPX-AP-A supports diagnostic options via PROFINET IO in accordance with
IEC 61158, e.g. module-related and channel-related status information as well as error detection in the
online mode of the control software and in the user program of the high-order controller.
Diagnostic messages from the automation system CPX-AP-A that cannot be seen on the PROFINET
standard diagnostics are shown as manufacturer-specific PROFINET channel diagnostics.
For PROFINET, only the lower 16 bits of the diagnostics ID (error number) are shown.
The display rule is as follows:
–
Error number 1 … 32767:
ChannelErrType = 2001 with ExtChannelErrType = error number
–
Error number 32768 … 65535:
ChannelErrType = 2002 with ExtChannelErrType = error number – 32768
The error number 0 is reserved.
Information on grouping and displaying the diagnostic messages
è
Instructions for the automation system CPX-AP-A.