Festo — CPX-AP-A-PN-M12 — 2022-07
Technical data
25
Power supply
Logic supply PS
[V DC]
24
_
25%
Intrinsic current consump-
tion at nominal operating
voltage 24 V from PS
[mA]
Typically 80
Reverse polarity protection
24 V PS against 0 V PS
Yes
Diagnostics message, over-
voltage in logic supply PS
[V DC]
³
31
Electrical isolation supply
Isolation present
Mains buffering time, logic
supply PS
[ms]
10
Load supply PL
[V DC]
24 ± 25%
Intrinsic current consump-
tion at 24V at nominal
voltage 24 V from PL
[mA]
Typically 4
Reverse polarity protection
24 V PL against 0 V PL
Yes
Diagnostics message, under-
voltage in load supply PL
[V DC]
£
17
Diagnostics message, over-
voltage in load supply PL
[V DC]
³
31
Tab. 17: Power supply