22
Festo — CPX-AP-A — 2022-07
Installation
Connecting elements M12
System supply
Plug M12, 5-pin, L-coded
Signal
1
+24 V DC logic supply PS
2
0 V DC logic supply PS
3
+24 V DC load supply PL
4
0 V DC load supply PL
FE
Functional earth FE
Tab. 11: System supply
Additional supply
Plug M12, 5-pin, L-coded
Signal
1
-
2
-
3
+24 V DC load supply PL
4
0 V DC logic supply PL
FE
Functional earth FE
Tab. 12: Additional supply
Forwarding supply
M12 socket, 5-pin, L-coded
Signal
1
+24 V DC logic supply PS
2
0 V DC logic supply PS
3
+24 V DC load supply PL
4
0 V DC load supply PL
FE
Functional earth FE
Tab. 13: Forwarding supply