Festo — CPX-AP-A — 2022-07
Installation
23
Connecting elements M18
System supply
Plug M18, 4-pin
Signal
1
+24 V DC logic supply PS
2
+24 V DC load supply PL
3
0 V (DC load supply PL + DC logic supply PS)
4
Functional earth FE
Tab. 14: System supply
Additional supply
Plug M18, 4-pin
Signal
1
-
2
+24 V DC load supply PL
3
0 V DC load supply PL
4
Functional earth FE
Tab. 15: Additional supply
Connecting elements push-pull
System supply
Push-pull plug, 5-pin
Signal
1
+24 V DC logic supply PS
2
0 V DC logic supply PS
3
+24 V DC load supply PL
4
0 V DC load supply PL
5
Functional earth FE
Tab. 16: System supply
Additional supply
Push-pull plug, 5-pin
Signal
1
-
2
-
3
+24 V DC load supply PL