5. Analogue output module CPX−2AA−U−I
5−24
Festo P.BE−CPX−AX−EN en 0503b
M
od
u
l
e
p
a
r
amete
r
s
: F
ai
l
sa
f
e
c
h
anne
l x
Function no.
Access to these module parameters is made via protocol−specific functions
(see the manual for the field bus node).
Description
With the aid of the so−called Fail safe parametrizing, you can specify the signal
status which the outputs are to assume in the event of field bus communication
faults (see also CPX system manual). This can be accomplished with the follow
ing parameters:
Fault mode channel x
Fault state channel x
Values
Fault mode channel x:
0 = Hold last state
1 = Fault state (presetting)
Fault state channel x:
0 = Reset value (presetting)
1 = Set value
Remark
The parametrizing of the fault mode for an analogue output channel depends on
the field bus protocol and is carried out:
by an individual parameter setting or bit (e.g. CPX−FB11),
by setting all parameter bits of the relevant word (e.g. CPX−FB6) to Hold last
state" or Fault state".
For parametrizing the Fault state, the desired output word must be correspon
dingly mapped in the parameter bits Fault state channel x".
The Fail safe reaction is determined for the complete CPX terminal by means of
the system parameter Fail safe" (see CPX system manual).
Tab.5/16:
Fail safe channel x (channel−specific)
Summary of Contents for CPX-2AA-U-I
Page 2: ......
Page 19: ...Overview and connection technology I O modules 1 1 Festo P BE CPX AX EN en 0503b Chapter 1...
Page 44: ...1 Overview and connection technology I O modules 1 26 Festo P BE CPX AX EN en 0503b...
Page 45: ...Analogue input module CPX 2AE U I 2 1 Festo P BE CPX AX EN en 0503b Chapter 2...
Page 83: ...Analogue input module CPX 4AE I 3 1 Festo P BE CPX AX EN en 0503b Chapter 3...
Page 122: ...3 Analogue input module CPX 4AE I 3 40 Festo P BE CPX AX EN en 0503b...
Page 123: ...Analogue input module CPX 4AE T 4 1 Festo P BE CPX AX EN en 0503b Chapter 4...
Page 157: ...Analogue output module CPX 2AA U I 5 1 Festo P BE CPX AX EN en 0503b Chapter 5...
Page 198: ...5 Analogue output module CPX 2AA U I 5 42 Festo P BE CPX AX EN en 0503b...
Page 199: ...Technical appendix A 1 Festo P BE CPX AX EN en 0503b Appendix A...
Page 221: ...Index B 1 Festo P BE CPX AX EN en 0503b Appendix B...
Page 222: ...B Index B 2 Festo P BE CPX AX EN en 0503b Contents B Index B 1...