2. Analogue input module CPX−2AE−U−I
2−34
Festo P.BE−CPX−AX−EN en 0503b
F
au
l
t
num
b
e
r
D
esc
r
i
p
ti
o
n
F
au
l
t
t
r
eatment
10
R
ate
d r
an
g
e
e
x
cee
d
e
d
1)
Upper limit exceeded.
(See parameter Upper limit channel x
low byte/high byte" or Monitoring
channel x monitoring rated range
exceeded")
·
Check signal range of input.
·
Check input signal present.
·
Check parametrized limit.
·
If necessary, deactivate monitoring.
15
M
od
u
l
e
/
c
h
anne
l f
ai
l
e
d
2)
General fault, module faulty.
·
Power off/on necessary
·
If this fault occurs again: check and, if
necessary, replace the analogue input
module.
Evaluation of the analogue input signals
has stopped.
21
23
24
25
F
au
l
t
in
p
a
r
amet
r
i
z
in
g
1) 3)
A fault has occurred in the setting of the
relevant parameter.
Parameter data format
Parameter measured value smoothing
Parameter lower limit
Parameter upper limit
(See parameter Monitoring the CPX
module monitoring parametrizing fault"
or Monitoring channel x monitoring
parametrizing fault")
·
Check the parametrizing undertaken
and, if necessary, undertake the
parametrizing again with the correct
parameters (valid parameters see
section 2.4.3).
The analogue input module will be
operated further with the last valid
parametrizing.
1)
The module displays the relevant fault depending on the parametrizing. The analogue input
signals, however, will be processed further.
2)
Processing of the analogue input signals will be stopped.
3)
The parameters entered will be ignored, the module operates with the last valid parameters.
Tab.2/21:
Fault messages of the input modules part 2
Pl
ease
n
o
te
Please note the following when using the input modules:
If there is a short circuit, all sensor supplies of the
module will be switched off
t
og
et
h
e
r
.
If not parametrized otherwise, the sensor supply voltage
will be switched on again
aut
o
matica
lly
when the short
circuit is eliminated.
Summary of Contents for CPX-2AA-U-I
Page 2: ......
Page 19: ...Overview and connection technology I O modules 1 1 Festo P BE CPX AX EN en 0503b Chapter 1...
Page 44: ...1 Overview and connection technology I O modules 1 26 Festo P BE CPX AX EN en 0503b...
Page 45: ...Analogue input module CPX 2AE U I 2 1 Festo P BE CPX AX EN en 0503b Chapter 2...
Page 83: ...Analogue input module CPX 4AE I 3 1 Festo P BE CPX AX EN en 0503b Chapter 3...
Page 122: ...3 Analogue input module CPX 4AE I 3 40 Festo P BE CPX AX EN en 0503b...
Page 123: ...Analogue input module CPX 4AE T 4 1 Festo P BE CPX AX EN en 0503b Chapter 4...
Page 157: ...Analogue output module CPX 2AA U I 5 1 Festo P BE CPX AX EN en 0503b Chapter 5...
Page 198: ...5 Analogue output module CPX 2AA U I 5 42 Festo P BE CPX AX EN en 0503b...
Page 199: ...Technical appendix A 1 Festo P BE CPX AX EN en 0503b Appendix A...
Page 221: ...Index B 1 Festo P BE CPX AX EN en 0503b Appendix B...
Page 222: ...B Index B 2 Festo P BE CPX AX EN en 0503b Contents B Index B 1...