1. Installation
1−11
Festo P.BE−CP−SD8−...−EN en 0503b
1.3
Connecting the CPV valve terminal
1.3.1 Connecting cable
Field bus cable
S
Use a 4−wire cable for the field bus connection as speci
fied for your control system. The bus interface and the
internal logic of the CPV valve terminal are supplied with
power via the field bus cable.
Load voltage supply
S
Use a 2−wire cable for supplying the load voltage to the
CPV valve terminal. Screening is not necessary.
Please note
S
You must refer to the PLC/IPC manual or the manual for
your bus interface in order to ascertain the type of field
bus cable which you should use. Take into account here
the distance and the baud rate.
S
Select the appropriate cross−sectional area and observe
the voltage drop:
on the supply cable (field bus cable) for the bus
interface/internal logic and
on the supply cable for the CPV valves.
Summary of Contents for Compact Performance CPV Series
Page 2: ......
Page 4: ...Contents and general safety instructions II Festo P BE CP SD8 EN en 0503b...
Page 12: ...Contents and general safety instructions X Festo P BE CP SD8 EN en 0503b...
Page 13: ...Installation 1 1 Festo P BE CP SD8 EN en 0503b Chapter 1...
Page 38: ...1 Installation 1 26 Festo P BE CP SD8 EN en 0503b...
Page 39: ...Commissioning 2 1 Festo P BE CP SD8 EN en 0503b Chapter 2...
Page 48: ...2 Commissioning 2 10 Festo P BE CP SD8 EN en 0503b...
Page 49: ...Diagnosis 3 1 Festo P BE CP SD8 EN en 0503b Chapter 3...
Page 60: ...3 Diagnosis 3 12 Festo P BE CP SD8 EN en 0503b...
Page 61: ...Technical Appendix A 1 Festo P BE CP SD8 EN en 0503b Appendix A...
Page 68: ...A Technical Appendix A 8 Festo P BE CP SD8 EN en 0503b...
Page 69: ...Index B 1 Festo P BE CP SD8 EN en 0503b Appendix B...
Page 70: ...B Index B 2 Festo P BE CP SD8 EN en 0503b Contents Index B 1...