1. Installation
1−21
Festo P.BE−CP−SD8−...−EN en 0503b
Bus length
The table below shows guidelines for the maximum distance
as a factor of the baud rate selected. Exact specifications can
be found in the manuals for your control system or bus inter
face.
Baud rate
Maximum
distance
Max. branch
line length
1000 kBaud
10 − 40 m
0.3 m
500 kBaud
50 − 100 m
0.75 m
125 kBaud
500 m
3 m
20 kBaud
1000 m
7.5 m
Bus supply
Avoid long distances between the bus interface/logic supply
and the CPV valve terminal.
Please note
Bus slaves have different tolerances in respect of the inter
face supply, depending on the manufacturer. You must
take this into account when planning the bus length and
placing the power unit.
Recommendation:
Place the power unit in the centre of the bus. The following
tolerance for the bus interface supply applies to Festo CPV
valve terminals:
V
max
= 25 V
V
min
= 11.5 V
Summary of Contents for Compact Performance CPV Series
Page 2: ......
Page 4: ...Contents and general safety instructions II Festo P BE CP SD8 EN en 0503b...
Page 12: ...Contents and general safety instructions X Festo P BE CP SD8 EN en 0503b...
Page 13: ...Installation 1 1 Festo P BE CP SD8 EN en 0503b Chapter 1...
Page 38: ...1 Installation 1 26 Festo P BE CP SD8 EN en 0503b...
Page 39: ...Commissioning 2 1 Festo P BE CP SD8 EN en 0503b Chapter 2...
Page 48: ...2 Commissioning 2 10 Festo P BE CP SD8 EN en 0503b...
Page 49: ...Diagnosis 3 1 Festo P BE CP SD8 EN en 0503b Chapter 3...
Page 60: ...3 Diagnosis 3 12 Festo P BE CP SD8 EN en 0503b...
Page 61: ...Technical Appendix A 1 Festo P BE CP SD8 EN en 0503b Appendix A...
Page 68: ...A Technical Appendix A 8 Festo P BE CP SD8 EN en 0503b...
Page 69: ...Index B 1 Festo P BE CP SD8 EN en 0503b Appendix B...
Page 70: ...B Index B 2 Festo P BE CP SD8 EN en 0503b Contents Index B 1...