9. Service functions and error messages
Festo P.BE-CMMP-AS-3A-HW-EN 0708NH
97
Error message
Meaning of error message
Measures
Main index
Main
index
Sub-
index
2
I²t PFC
Check power dimensioning of drive. Select operation
without PFC?
3
I²t- braking resistor
Braking resistor overloaded.
Use external braking resistor?
32
0
Intermediate circuit charging
time exceeded
Please contact Technical Support .
1
Undervoltage for active PFC
5
Brake chopper overload.
Intermediate circuit could not be
discharged
6
Intermediate circuit discharge
time exceeded
7
Power supply missing for
controller enable
Intermediate circuit voltage missing.
Angle encoder not yet ready.
8
Power supply failure on
controller enable
Interruption / Mains failure of the power supply
Check the power supply.
9
Phase failure
Failure in one or more phases.
Check the power supply.
33
0
Contouring error encoder
emulation
Please contact Technical Support.
34
0
No synchronisation via Fieldbus Synchronisation messages from master failed?
1
Fieldbus synchronisation error
Synchronisation messages from master failed?
Synchronisation interval parameterised too small?
35
0
Linear motor spin protection
Encoder signals are faulty. Check installation for EMC
recommendations.
5
Error in determination of com-
mutator position
An unsuitable process was selected for the motor.
Please contact Technical Support.
36
0
Parameter was limited
Check the user parameter record.
1
Parameter was not accepted
37
0 ... 9
SERCOS Fieldbus
Please read the SERCOS manual and, if necessary,
contact Technical Support.
38
0 ... 9
SERCOS Fieldbus
Please read the SERCOS manual and, if necessary,
contact Technical Support.
39
0 ... 9
SERCOS Fieldbus
Please read the SERCOS manual and, if necessary,
contact Technical Support.
40
0
Negative SW limit switch
reached
The positioning setpoint has reached or exceeded the
respective software limit switch.
Check the target data.
Check the positioning range.
1
Positive SW limit switch reached
Summary of Contents for CMMP-AS-C2-3A