9. Service functions and error messages
Festo P.BE-CMMP-AS-3A-HW-EN 0708NH
95
Error message
Meaning of error message
Measures
Main index
Main
index
Sub-
index
4
Identification does not support
the configured device type
Identification using the parameterised angle encoder
settings could not be performed.
Check the angle encoder configuration and, if neces-
sary, contact Technical Support.
5
Zero impulse not found
The zero impulse was not found after the maximum
permissible number of electrical rotations.
Check the zero impulse signal.
6
Hall-effect signal invalid
The impulse sequence or segmentation of the hall-
effect signal is unsuitable.
Check the connection and, if necessary, contact Tech-
nical Support.
7
Identification not possible
Ensure adequate intermediate circuit voltage.
Rotor blocked?
8
Invalid number of pole pairs
The calculated number of pole pairs lies outside the
parameterisable range. Check the motor technical
data and, if necessary, contact Technical Support.
9
Automatic parameter identifica-
tion
General error
Obtain additional information from the additional
error data. Please contact Technical Support.
15
0
Division by 0
Please contact Technical Support.
1
Range exceeded
2
Mathematical underrun
16
0
Error in program execution
Please contact Technical Support.
1
Illegal interrupt
2
Initialisation error
3
Unexpected status
17
0
Contouring error limit exceeded Increase error window.
Acceleration parameter too large.
1
Encoder difference monitoring
External angle encoder not connected or defective?
Deviation fluctuates, e.g. due gear backlash, if neces-
sary, increase cut-off threshold.
21
0
Error 1 current measurement U
Error cannot be self-corrected.
Send the servo positioning controller to your sales
partner.
1
Error 1 current measurement V
2
Error 2 current measurement U
3
Error 2 current measurement V
22
0
PROFIBUS:
Error on initialisation
Defective technology module?
Please contact Technical Support.
1
PROFIBUS: Reserved