CESA-GW-AS-PB Description
51
The AS-i safety monitor diagnostics function reads the diagnostics data from the
AS-i safety monitor and displays these data. The significance of the displayed di-
agnostics and of the setting SORTED/V1, UNSORTED is described in the oper-
ating manual of the safety monitor.
6.12.3
SAFETY SUBST VAL (Substitute values for input data from safe slaves)
Main menu || AS-I SAFETY || SAFETY SUBST VAL ||
This function enables activation/deactivation of the code substitute function for
safe slaves.
SUBSTITUTE (values)
The safety code sequences are replaced by the following values:
NO SUBSTITUTE
The safety code sequences are transmitted via the input data.
SAFETY MONITOR
DIAGNOSIS
ADDR: 17
MODE: SORT./V1
STATUS: OK
CHANNEL 1: OFF
CHANNEL 2: OFF
1-32: GREEN
…
SAFE SUBST VAL
SUBSTITUTE
CHANGE
Both channels are in the safe state: 0000bin
Channel 1 is in the safe state: 0011bin
Channel 2 is in the safe state: 1100bin
No channel is in the safe state: 1111bin