CESA-GW-AS-PB Description
46
This function displays the status of the actual configuration of the individual AS-i
slaves.
A help appears at the end of the list explaining the abbreviations:
After selecting the desired AS-i slave address, the values for the current configu-
ration data are displayed after the respective address in the following order:
•
IO (I/O-Configuration)
•
ID (ID-Configuration)
•
xID1 (extended ID1)
•
xID2 (extended ID2).
In addition, the status of the configuration is shown in plain text.
If no AS-i slave is present at an address and none is designed in, four decimal
points are displayed instead of the configuration data.
6.10.3
LPF (List of Peripheral Faults)
Main menu|| DIAGNOSIS ||
LPF
LIST OF PERIPH. FAULTS
||
This list shows the list of slaves which have triggered peripheral faults (LPF).
X (O.K.): The configuration data for the detected AS-i slave agree with
the designed in configuration data.
D (Detected Only): An AS-i slave is detected at this address, but it was not
designed in.
P (Projected Only): An AS-i slave was designed in at this address, but it was not
detected.
C (Type Conflict): The configuration data for the detected AS-i slave do not
agree with the designed in configuration data. The actual exist-
ing configuration of the connected AS-i slave is displayed.
F (Periph. Fault): The AS-i slave has a peripheral error.
A (Duplicate Adr.): Two AS-i slaves at the indicated address.
0A - .... -
1A - 7A28 -C
WRONG TYPE
LPF LIST OF
PERIPH. FAULTS
| 1A-X
2A- | 3A-
4A-X | 5A-X
....
30A-X | 31A-
| 1B-X