BLUEHELIX TOP RRT K 50
239
EN
cod. 3541Q281 - Rev. 02 - 10/2020
b11
Hot water tank preparation
mode
0
= Fixed primary
1
= Linked setpoint
2
= Ramp
0
b12
Override priority - Activation
0-255 minutes
30
b13
Override priority - Deactivation
0-255 minutes
15
b14
Pump antiblock operation time
0-20 seconds
5
b15
No effect on adjustment
0
=Flow. (450 imp/l)
1
=Flow. (700 imp/l)
2
= Flow (190 imp/l)
2
b16
Fan frequency in standby mode 0-100%
0%
b17
Summer/Winter symbol
0
= Disabled
1
= Enabled
0
b18
No effect on adjustment
0-100L/min/10
25
b19
No effect on adjustment
0-100L/min/10
20
b20
Flue material selection
0
= Standard
1
= PVC
2
= CPVC
0
b21
PVC flue maximum temperature 60-110°C
88°C
b22
CPVC flue maximum tempera-
ture
60-110°C
93°C
b23
Standard flue shutdown maxi-
mum temperature
60-110°C
100°C
b24
PVC flue shutdown maximum
temperature
60-110°C
93°C
b25
CPVC flue shutdown maximum
temperature
60-110°C
98°C
b26
Flow temperature limit in auto-
matic calibration
25°C ÷ 55°C
30°C
b27
Maximum temperature during
calibration in DHW mode
75°C ÷ 95°C
80°C
b28
No effect on adjustment
0 ÷ 60 (0 = disabled)
20
b29
Restoring Factory Values
Change the value from 0 to 10 by pressing the
“DHW +”
button.
Confirm by pressing the
“h”
button.
-
P30
Heating ramp
1-20°C/minute
4°C/minute
P31
Virtual setpoint min. tempera-
ture
0
= Deactivated
1-80°C
0
P32
Heating standby time
0-10 minutes
4
P33
Heating Post-Circulation
0-255 minutes
15
P34
Pump operation
0-3 = Operation strategy
2
P35
Modulating pump min. speed
30-100%
30%
P36
Modulating pump start speed
90-100%
90%
P37
Modulating pump max. speed
90-100%
100%
P38
Pump deactivation temperature
during Post-Circulation
0-100°C
55°C
P39
Pump activation hysteresis tem-
perature during Post-Circulation
0-100°C
25°C
P40
Heating user max. setpoint
20-90°C
80°C
P41
Max. output in heating
0-100%
80%
P42
Legionella protection
0 ÷ 7 = Activation days
0
= Disabled
1
= Once every 24 hours .....
7
= Once every 168 hours
0
P43
Hot water tank hysteresis
0-60°C
2°C
P44
Primary setpoint
70-85°C (Primary circuit temperature adjustment in DHW)
80°C
Contents Description
Range
Default