BLUEHELIX TOP RRT K 50
238
EN
cod. 3541Q281 - Rev. 02 - 10/2020
If the TEST mode is active and there is a DHW demand (by drawing hot water), the boiler remains in TEST mode but
the 3-way valve goes to DHW.
To deactivate the TEST mode, simultaneously press the heating buttons (details 3 and 4 - fig. 1) for 5 seconds.
The TEST mode is automatically disabled in any case after 15 minutes or by not drawing hot water (if enough hot water
has been drawn to activate the DHW mode).
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 3.1). Press the heating buttons detail 3 - fig. 1
to increase or decrease the power (min. = 00 - max. = 100). Press the
reset
button within 5 seconds and the max. power
will remain that just set. Exit TEST mode (see sec. 3.1).
Service menu
ONLY QUALIFIED PERSONNEL CAN ACCESS THE SERVICE MENU AND MODIFY PARAMETERS.
The card Service Menu is accessed by pressing the Reset button for 10 seconds.
The display will show: "100" and "co" flashing.
Then set "103" with the DHW buttons, with the heating buttons set "123" and confirm by pressing the Reset button.
Five submenus are available: press the Heating buttons to select, in increasing or decreasing order,
“tS”, “sC”, “In”,
“Hi”
or
“rE”
.
To access the selected menu, press the
reset
button once.
“tS” - Transparent Parameters Menu
Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to
view or modify the value of a parameter: the change will be automatically saved.
Contents Description
Range
Default
b01
Boiler type selection
1
= BITHERMAL INSTANTANEOUS
2
= MONOTHERMAL HEATING only (also with OPTIONAL HOT WATER
TANK)
3
= MONOTHERMAL COMBI
4
= MONOTHERMAL with HOT WATER TANK
4
b02
Exchanger type
1 ÷ 4
Model
28 K 50
: 2
Model 34 K 50
: 3
b03
Absolute Maximum Heating
Power
0 ÷ 100%
(Do not modify the value)
85%
b04
System water pressure protec-
tion selection
0
= Pressure switch
1
= Pressure transducer
0
b05
Summer/Winter mode
0
= WINTER - SUMMER - OFF
1
= WINTER - OFF
0
b06
Variable input contact opera-
tion selection
0
= Continuous Comfort
1
= System thermostat
2
= Second room thermostat
3
= Warning/Alert
4
= Safety thermostat
2
b07
Relay card LC32 selection
0
= External gas valve
1
= Alarm
2
= System filling solenoid valve
3
= Solar 3-way valve
4
= Second heating pump
5
= Alarm2
6
= Burner On
7
= Frost protection active
0
b08
No effect on adjustment
0-24 hours (time for temporary deactivation of comfort mode without
drawing)
24
b09
Fault 20 status selection
0
= Deactivated
1
= Enabled (only for versions with pressure transducer)
0
b10
Not implemented
--
--