11.1. Supply point
Please connect the 230V current supply to the terminals located on the mounting plate. A suitable
cable type would be a standard 3x1,5mm
2
cable
.
Please connect the protective conductor to the appropriate terminal X5.3 (PE)
.
11.2. Circuitry of the relay outputs
The evaluation unit has 2 relay outputs, which can be used as make contact or break contact. De-
tection of an authorized transponder is emitted as a pulse at relay 1 – pulse duration may be freely
adjusted – and generally serves as a trigger signal for barriers, door openers etc. Relay 2 makes
contact as soon as a non-authorized ID-code has been identified. All relay connections are on ter-
minal strip X4.
Configuration of terminal strip X4 – relay outputs
Terminal
Name
Explanation
X 4.1
ON
Make contact of relay 1
X 4.2
OFF
Break contact of relay 1
X 4.3
COM
Common connection relay 1
X 4.4
ON
Make contact of relay 2
X 4.5
OFF
Break contact of relay 2
X 4.6
COM
Common connection relay 2
Chart 4:
Terminal strip X4