Locating the Steam Generator Unit
IMPORTANT NOTE:
The control cables should be run in dedicated 1" conduit to
facilitate installation and service Select a location as near as practical to the steam room.
Typical locations include: closet, vanity cabinet, heated attic or basement.
The maximum length of the MSTS is 60 feet. MSTS connects to the steam
generator and is required to be installed inside the steam room when the control is mounted
outside the steam room.
(
Items 1-7)
1. DO NOT install steambath generator or plumbing lines in unheated attic or any
locations where water could freeze.
2. DO NOT install steambath generator inside steam room.
3. DO NOT install steambath generator outdoors or wherever environmental condi-
tions may affect the safety and/or performance of the generator.
4. DO NOT install steambath generator near flammable or corrosive materials or
chemicals such as gasoline, paint thinners, or the like. Installation in areas having
high concentrations of chlorine (such as pool equipment room) must be avoided.
5. Install steambath generator on a solid and level surface. Provide supports under
steam generator when wall mounting. Keyhole slots are provided for wall mounting.
Insure the steam generator is properly secured and level when mounting with
keyhole slots.
6. Install steambath generator in an upright position only.
7. Burn Hazard. Steam piping, safety valve, drain valve, plumbing and steamheads
become hot during operation and remain hot after shutdown for a period of
time. Provide appropriate protection, including insulating plumbing lines.
Avoid plumbing runs and steamhead locations that can come in contact
with bathers.
IMPORTANT NOTE:
(
Items 8-11)
8. Install anti-water hammer device as necessary.
9. Provide a minimum of 12 inches at both ends and
top of the steam generator or as required for servicing. See page 8.
10. Provide unions as required to facilitate installation and disconnection of piping.
11. The controls should be placed in a location only accessible by the facility’s staff.
The CT SteamStop
®
and remote sensor are required to be installed inside the
steamroom.
MrSteam Generators and controls are CE and UL listed.
The CT series of steam generators are for commercial use only.