ELECTRICAL DATA
120/208-240 Volt/ 60HZ/ 1PH
Model
Total Amps
SN4HD
30Amps
SN6HD
45Amps
The case must be wired to a 208 through 240 VAC, single phase, three wire electrical source.
Only copper wire can be used for the power supply connections.
Incoming wire size requirements for the Series ’90 Hot Deli Models are as follows:
Models:
SN4HD
#10AWG Copper Wire
SN6HD
#8AWG Copper Wire
The case must also be wired to a 115 VAC, single phase, three wire electrical source for the general purpose
receptacle.
Units are intended for permanent field connection only. Electrical installation must be in accordance with all
national, state, and local electrical codes, and must be performed by qualified electrical personnel.
Models are equipped with a general purpose receptacle requiring separate electrical circuit installed in
accordance with National Electrical Code.